SETTING
BASIC SETTINGS
Setpoint Pressure
Sleep Frequency
Sleep Delay Time
Minimum Frequency
Maximum Frequency
Lead Pump Start Differential Pressure
Lag Pump Start Differential Pressure
Lag Pump Stop Differential Pressure
Alternation
Alternation Time
Low Pressure Alarm
Low Pressure Alarm Delay Time
Low Pressure Alarm Reset Delay Time
High Pressure Alarm
Low Water Delay Time
PUMP SETTINGS
Acceleration
Deceleration
Thrust Bearing Frequency
Thrust Bearing Acceleration
Pump 1 Overload Amps
Pump 1 Motor Voltage
Pump 2 Overload Amps
Pump 2 Motor Voltage
Pump 3 Overload Amps
Pump 3 Motor Voltage
ADVANCED SETTINGS
Sensor Range
Sensor Offset
PID Proportional Term
PID Integral Term
PID Derivative Term
Setpoint Pressure 2
Pipe Fill Frequency
Pipe Fill Time
Low Suction Delay Time
Low Suction Reset
Low Suction Reset Delay Time
Idle Prevention Exercise Schedule
Pump 1 Jockey
Jockey Pump Stop Delay Time
Number of Pumps
Maximum Pumps On
Relay 1 Function
Relay 2 Function
Relay 3 Function
Relay 4 Function
Relay 5 Function
Relay 6 Function
VFD 1 Hand Speed
VFD 2 Hand Speed
VFD 3 Hand Speed
Language
*1 - Value based on "Sensor Range" setting
*2 - Value based on "Maximum Frequency" setting
*3 - Value based on output rating of variable frequency drive
*4 - Settings include: P1 Run, P2 Run, P3 Run, P1 Fault, P2 Fault, P3 Fault, High Press, Low Press, Low Suction, Low Water, General Alarm
SJE
®
CONTROLLER SETPOINTS LIST
STATION NAME
START UP DATE
CONTROLLER REVISION
MIN
MAX
0.0
*1
0.0
*2
0.0
999.9
0.0
*2
0.0
65.0
*1
0.0
*1
0.0
0.0
*1
Alternate/P1 Lead/P2 Lead/P3 Lead
1.0
999.9
0.0
*1
0.0
999.9
0.0
999.9
0.0
*1
0.0
999.9
0.0
3600.0
0.0
3600.0
0.0
*2
0.0
3600.0
0.0
999.9
0.0
999.9
0.0
999.9
0.0
999.9
0.0
999.9
0.0
999.9
1.0
999.9
-999.9
999.9
0
999
0
999
0
999
0.0
*1
0.0
*2
0.0
999.9
0.0
999.9
AUTO/MANUAL
0.0
999.9
0.0
999.9
ENABLED/DISABLED
0
999
1
3
1
3
*4
*4
*4
*4
*4
*4
0.0
*2
0.0
*2
0.0
*2
ENGLISH/ESPAÑOL
UNITS
DEFAULT
PSI
60.0
Hz
35.0
Seconds
10.0
Hz
30.0
Hz
60.0
PSI
-5.0
PSI
-7.0
PSI
7.0
Alternate
Hours
24.0
PSI
15.0
Seconds
20.0
Minutes
0.0
PSI
75.0
Seconds
10.0
Seconds
3.0
Seconds
3.0
Hz
0.0
Seconds
2.0
Amps
*3
Volts
*3
Amps
*3
Volts
*3
Amps
*3
Volts
*3
PSI
200.0
PSI
0.0
70
35
1
PSI
40.0
Hz
30.0
Seconds
0.0
Seconds
10.0
AUTO
Seconds
10.0
Days
0.0
DISABLED
Seconds
0
3
3
GEN. ALARM
HIGH PRESS
LOW PRESS
P1 RUN
P2 RUN
P3 RUN
Hz
45.0
Hz
45.0
Hz
45.0
ENGLISH
5
VFDC-3000 Controller User Manual
USER SETTING