Connection, lower level
Valve configu-
Evaporator Line
ration no.
Liquid feed line
Hotgas defrost line
Defrost drain line
1
Wet return line
Fan
Liquid feed line
Hotgas defrost line
2
Defrost drain line
Wet return line
Fan
Liquid feed line
Hotgas defrost line
3
Defrost drain line
Wet return line
Fan
Liquid feed line
Hotgas defrost line
4
Defrost drain line
Wet return line
Fan
2 | AN30561784681801-000101
ENGLISH
Network between
more EKE 400
H-R connection has
to be made on the
first and the last local
EKE 400.
EKE 400
Connection as close
as possible to the
connector
EKE 400
Valve selection in Wizard
Solenoid (ICFE)
Solenoid 2-step (ICSH)
Solenoid (upstream ICFD)
Solenoid 2-step (ICLX)
-
Solenoid (ICFE)
Solenoid (ICS)
Solenoid (upstream ICFD)
Solenoid 2-step (ICLX)
-
Solenoid (ICFE)
Solenoid 2-step (ICSH)
Solenoid for quick drain - pressurecontrol)
Solenoid 2-step (ICLX)
-
Solenoid (ICFE)
Solenoid (ICS)
Solenoid for quick drain - pressurecontrol)
Solenoid 2-step (ICLX)
-
Connection, upper level
Examples
1 AKS 33 pressure transmitter
1 Pt 1000 temp. sensor
Electric noise
Signal cables for sensors, DI inputs, data communication
and display must be kept separate from high voltage
(230 V) electric cables:
- Use separate cable trays
- Keep a distance between high voltage and signal cables
of at least 10 cm
Cables for DI input.
Cables longer than 10 meter (33 ft) is not recommended.
At cables longer than 10 meter (33 ft), it is recommended
to use auxiliary relays, placed within 10 meter (33 ft) cable
distance. Typical auxiliary relays then are placed in the
same panel, as EKE 400.
Parameter number DO1 DO2 DO3 DO4 DO5 DO6
R02
D2A
D1B and D4A
D3A
F01
R02
D2A
D1B and D4A
D3A
F01
R02
D2A
D1B and D4A
D3A
F01
R02
D2A
D1B and D4A
D3A
F01
Warning
The supply voltage of AI may not
share the signal with other controllers.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
© Danfoss | DCS (vt) | 2019.05