Time Alarm; Level Control; Flow Control - CPA EL 10 pH-rx Manual De Regulatión

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

TIME ALARM

MOD
l/h 1 unit
EL-PH/RX 04/12
EL-PH/RX 04/18
EL-PH/RX 05/10
EL-PH/RX 06/15
EL-PH/RX 10/2
10 166.6cc
EL-PH/RX 26/2
26 433.3cc
EL-PH/RX 30/1
30 500cc

LEVEL CONTROL

The closing of the level input contact, free of tension, while the pump is working, will cause:
1) the dosing stops
2) the green ON led blinks
3) the display shows "Level" alternatively on the first row and the actual measure on the second
When the level contact gets opened again, the pump returns to working mode compatible with
the actual inputs. NOTE: The level alarm suspends (but not reset) the counting of the Alarm
Time.

FLOW CONTROL

The closing of the flow input contact, free of tension, will cause:
1) the dosing stops
2) the green ON led blinks
3) The display shows "Flow" alternatively on the first row and the actual measure on the second
row.
When the flow contact gets opened again, the pump returns to working mode compatible with the
actual inputs. NOTE: The flow alarm resets the counting of the Alarm Time.
Rev 1.0
WHAT IS IT? The Time alarm is expressed in units (0-120unit) of dosage.
One unit is equivalent to 150 injections of chemical. The injections counting
starts from 0 when the pump starts dosing after the power on, increases
during dosing, stops during level alarm and stand_by state, and is resetted
when the power is off, when the measure reaches the setpoint and during the
flow alarm. When the counting reaches the value memorized in Time alarm
the pump goes in Time Alarm state:
1) The dosing stops (no tension to the electromagnet)
2) Green led On blinks
3) the display shows:"Tal" and the % flowrate on the first row and the
measure on the second row.
Push and hold ESC button for 2 seconds to esc the Time Alarm state and to
go back to functioning. The time alarm counting restart from 0 when the pump
starts dosing again
TIME ALARM EDITING
Push and quickly release CAL button and scroll the menu using + and –
buttons till the display shows "Alarm Time". Push CAL to enter the submenu
and then by pressing + and – button choice the value in units (0-120).
Push CAL to confirm and ESC to go back in measuring.
Alarm Time=
2000cc :(unit_cc)
4
66.6cc
30 unit
30 unit
4
66.6cc
24 unit
5
83.3cc
20 unit
6
100cc
12 unit
5 unit
4 unit
row.
Example for the calculation of Alarm Time to dose 2 liters
(=2000cc) of chemical at backpressure of the pump
nameplate.
NOTE: The time alarm has no effect on Manual mode
operation
Cod. 00.008.254
11