Maintenance & Cleaning; After Sales Care Support - Delabie PREMIX COMPACT 733015 Manual Del Usuario

Ocultar thumbs Ver también para PREMIX COMPACT 733015:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
NB: It is possible to adjust the temperature from 30 - 60°C by removing the control knob and turning
the notched spindle all the way in one direction or the other to achieve the desired temperature.
THERMAL & CHEMICAL SHOCKS
• PREMIX COMPACT is designed to withstand the thermal and chemical shocks recommended
within current regulations.
• To undertake a thermal shock (fig. D):
- Remove the covering cap a using a flat-headed screwdriver.
- Loosen the locking screw b using a Phillips screwdriver.
- Remove the control knob c by hand.
- Turn the notched spindle d ¾-turn to the left.
- Shut off the cold water supply.
- Once the thermal shock is complete, do not forget to re-set the temperature to the initial setting.
- Replace the control knob c.
SERVICING
Check the temperature setting and the anti-scalding safety at least twice a year (depending on the water quality).
To ensure continued reliability of the PREMIX, and to conform with local Anti-Legionella legislation,
we recommend checking the following at least twice a year:
• Non-return valves, filters and replaceable cartridge: de-scale or replace worn or damaged parts.
• Mixing chamber: de-scale.
If the PREMIX is not mixing correctly (fig. E):
• Balance the pressure. The pressure differential between the hot water and the cold water must be less
than 1 bar.
• Check the hot water supply temperature. The temperature should be higher than 55°C
• Shut off the water supply.
• Check that the filters f have been installed correctly. Replace if necessary
• Check the non-return valves e. Replace if necessary.
• The water supply must be connected using nuts with a compacted flange or a flat faced tap connector.
• To remove the mechanism:
- Unscrew the outlet nipple l using a 33mm spanner.
- Remove the spring k.
- Remove the water guide j.
- Remove the thermostatic element and the shuttle i by hand.
• Clean the thermostatic element and the shuttle i.
• Clean the mixer body interior.
• Check the O-ring.
• Replace the mechanism. Turn on the water supply. Always carry out a cold water failsafe check after
dismantling or carrying out maintenance.
MAINTENANCE & CLEANING
• Cleaning chrome: do not use abrasive, chlorine or any other acid-based cleaning products.
Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap several times to drain any remaining
water. In the event of prolonged exposure to frost, we recommend taking the mechanisms apart
and storing them indoors.
For the UK market only: Tel. 01491 821 821 - email: [email protected]
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: [email protected]

After Sales Care Support:

The installation guide is available on: www.delabie.co.uk