Technical Data
Pressure inputs
Channels
Pneumatic connection
Medium
Temp. range of the
medium
Measurement range
relative to the ambient
pressure
Measurement range for
differential pressure
calculation
Max. measurement range
for differential pressure
calculation
Max. permitted gauge
pressure range of the
pressure sensors
Pressure for sensor limit
diagnostic
14
CPX−4AE−P−D10
4
QS connect. for hose diameter 4 mm
Compressed air, filtered (40 m),
unlubricated or lubricated
0 ... +50 °C
0 ... 10 bar
0 ... 1000 kPa
0 ... 145 psi
−10 ... 10 bar
−1000 ... 1000 kPa
−145 ... 145 psi
−10.28 ... 10.28 bar
−1028 ... 1028 kPa
−149 ... 149 psi
15 bar
1500 kPa
217.5 psi
10.30 bar
1030 kPa
149.4 psi
Festo CPX−4AE−P 0906NH English
CPX−4AE−P−B2
−1 ... 1 bar
−100 ... 100 kPa
−14.5 ... 14.5 psi
−2 ... 2 bar
−200 ... 200 kPa
−29 ... 29 psi
−2.05 ... 2.05 bar
−205 ... 205 kPa
−30.4 ... 30.4 psi
5 bar
500 kPa
72.5 psi
1.051 bar
1051 kPa
15.24 psi