RWF 40
- Setting parameters
When the burner is ignited all displays of the regulator light up. The set point display will blink for about 10 seconds. The value in the
upper field of the display (red) indicates the actual value. The value in the lower field of the display (green) indicates the set point cur-
rently programmed.
CHANGING THE SET POINT
To change the set point, proceed as follows: -
Change the value of set point SP1 using the t and s keys.te s. -
turn to normal display press
* *
The value of SP1 depends on the value set previously in configuration level C111.
SETTING PID PARAMETERS
PID parameters are factory set to standard mean values. The operation of the regulator can be self-adapted to suit the system by acti-
vating the "tunE" function. The regulator will set the PID parameters automatically. To activate the "tunE" function proceed as follows:
-
-
With the burner in operation, press
adaptation routine has been completed. -
* *
The "tunE" function cannot be activated in Manual mode, or when the burner is off.
The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the deriva-
tive action time dt and the integral action time rt.
To change parameters Pb1, dt and rt, proceeds as follows: -
one parameter to the next, press
Confirm the changed parameters by pressing
cally. -
-
Press
PGM to access the next parameter. -
PGM
cess the next parameter. -
-
When rt is displayed, repeat the procedure above. -
DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows: -
the
PGM key to access the parameters level. -
PGM
ner ignition differential-stage II), increase or decrease the value using the t and s keys. -
sing
PGM. -
-
If confirmation is not given within 2 seconds the value will be stored automatically. -
PGM
parameter. -
-
When HYS2 is displayed (burner shutoff differential-stage II), repeat the procedure described above. -
cess the next parameter. -
-
When HYS3 is displayed (upper shutoff differential) repeat the procedure described above.
-
To return to normal display press
-
MANUAL/AUTOMATIC MODE
To access "MANUAL" mode, press and hold
operation. It is deactivated automatically when the burner shuts off. When the LED above the hand symbol is alight, the regulator is in
manual mode and the position of the servocontrol can be changed using the t and s keys. The LEDS on the front of the regulator in-
dicate whether the servocontrol OPEN or CLOSE command is currently active. Pressing the t key the servocontrol OPENS. Pressing
the s key the servocontrol CLOSES. To select automatic mode press and hold
symbol goes out and the regulator reverts to automatic.
CLIMATIC COMPENSATION
The RWF 40 regulator can be set with the set point interlocked to the external probe. To select this operating mode, proceed as fol-
lows: -
-
Connect the required probe as in the wiring diagram. -
gulator must be set as follows: -
use the s key to access the second figure (XXXX). Use the t key to select the type of probe (XX3X). -
meters by pressing
PGM. If this is not done within 2 seconds, the value is stored automatically -
PGM
tion level. When the display reads C112 (XXXX), use the s key to access the second figure (XXXX). Press the t key to set the type
of probe (XX3X). -
-
Confirm the changed parameters by pressing
stored automatically.
-
To return to normal display press
-
-
Press
PGM
PGM to access the parameters level. -
-
(heating curve gradient), increase or decrease the value using the t and s keys. -
PGM. -
-
If confirmation is not given within 2 seconds the value will be stored automatically.
PGM
-
-
To return to normal display press
420010480501
-
Press the
PGM button to access the user level. SP1* will appear in the lower display -
PGM
EXIT.
EXIT
PGM + t. -
PGM
-
the caption "tunE*" will blink in the display. – When "tunE" stops blinking, the self-
Confirm the computed parameters by pressing the s key for 2 seconds.
-
PGM . -
-
When Pb1 is displayed, the value can be increased or decreased using the s and t keys. -
PGM
PGM. -
PGM
-
If confirmation is not given within 2 seconds the value will be stored automati-
-
When dt is displayed, repeat the procedure described above. -
-
To move from one parameter to the next, press
EXIT.
EXIT
EXIT for at least 5 seconds. Manual mode can only be selected when the burner is in
EXIT
-
Press the
PGM key to access the configuration level. When the caption C111 (XXXX) is displayed,
PGM
EXIT. To establish the heating curve, proceed as follows:
EXIT
-
Press
PGM to move from one parameter to the next. -
PGM
EXIT.
EXIT
-
After a 2 second delay the value set is stored automatically – To re-
PGM button to access the parameters level. -
-
Press the
PGM
-
To return to normal display press
EXIT for at least 5 seconds. The LED above the hand
EXIT
-
Change the regulator settings. When using an external probe the re-
PGM. -
-
If confirmation is not given within 2 seconds the value will be
PGM
-
Confirm the changed parameters by pressing
-
To move from
-
Press PGM to ac-
EXIT.
EXIT
PGM . -
-
When HYS1 is displayed (bur-
PGM
-
Confirm the changed parameters by pres-
-
Press
PGM to access the next
PGM
-
Press
-
Confirm the change of para-
-
Press
PGM to access the configura-
PGM
-
When the letter H is displayed
www.ecoflam-burners.com
EN
-
-
-
Press
PGM to ac-
PGM
7