Manejo
6.6 Comunicación vía EtherNet/IP
Supervisor Object, Instance Number: 29 hex
Servicios soportados
Clase
Tabla 6- 24
N.°
1
2
3
Tabla 6- 25
N.°
3
5
6
7
9
10
11
12
13
14
15
224
• Get Attribute single
Class Attribute
Servicio
Tipo
Nombre
get
UINT16
Revision
get
UINT16
Max Instance
get
UINT16
Num of Instances
Instance Attribute
Servicio
Tipo
Nombre
get, set
Bool
Run1
get, set
Bool
Net Control
get
UINT8
State
get
Bool
Running1
get
Bool
Ready
get
Bool
Fault
get
Bool
Warning
get, set
Bool
Fault Reset
get
UINT16
Fault Code
get
UINT16
Warning Code
get
Bool
CtlFromNet
Instancia • Get Attribute single
• Set Attribute single
Valor/explicación
STW.0: Funcionamiento, giro horario
Interno
0: Local
1: Red
0: Vendor Specific
1: Startup
2: Not_Ready
3: Ready
4: Enabled
5: Stopping
6: Fault_Stop
7: Faulted
ZSW1:2
1: - (Enabled and Run1) or
- (Stopping and Running1) or
- (Fault_Stop and Running1)
0 = Other state
ZSW1:0
1: - Ready or
- Enabled or
- Stopping
0 = Other state
ZSW1:3: error de accionamiento
ZSW1:7: Alarma presente
STW.7: Confirmar fallo
r0945[0]: Código de error
r2122[0]: Código de alarma
Indicación de Net Control
1: Control from network
0: Local control
Instrucciones de servicio, 04/2016, A5E32923365A