Installation Drawing 6335QF01
Model 6335C, 6335D
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G
Class I, Zone 0, IIC
Ambient temperature limits
T6: -40 to + 60 deg. Celcius
S
Terminal 41,42,43,44
Vt or Uo: 9,6 V
E
It or Io: 28 mA
N
Pt or Po: 67.2 mW
S
Ca or Co: 3.5 uF
O
La or Lo: 35 mH
R
Ch 1
S
Terminal 51,52,53,54
Vt or Uo: 9,6 V
E
It or Io: 28 mA
N
Pt or Po: 67.2 mW
S
Ca or Co: 3.5 uF
O
La or Lo: 35 mH
R
Ch 2
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes
stipulated in The National Electrical Code (ANSI-NFPA 70).
When installed in Class II locations the Transmitter shall be installed in an enclosure
with a specified ingress protections of IP6X according to IEC60529 and Dust-tight
conduit seals must be used.
Equipment that is FM-approved for intrinsic safety may be connected to barriers
based on the ENTITY CONCEPT. This concept permits interconnection of approved
transmitters, meters and other devices in combinations which have not been
specifically examined by FM, provided that the agency's criteria are met. The
combination is then intrinsically safe, if the entity concept is acceptable to the
authority having jurisdiction over the installation.
The entity concept criteria are as follows:
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(V
MAX
which the device can receive and remain intrinsically safe, must be equal to or
6335QF01revAC.doc
2005-12-16
18
Non Hazardous Location
Um < 250V
Terminal 11, 14
Voc or Uo < Vmax or Ui
Vmax or Ui: 30 V
Isc or Io < Imax or Ii
Imax or Ii: 120 mA
Po < Pi
Pmax or Pi: 0.84 W
Ca or Co > Ci + Ccable
Ci: 1 nF
La or Lo > Li + Lcable
Li:10 uH
+
Associated Apparatus
or Barrier
with
-
entity Parameters:
+
Associated Apparatus
or Barrier
with
-
entity Parameters:
Terminal 21, 24
Um < 250V
Vmax or Ui: 30 V
Voc or Uo < Vmax or Ui
Imax or Ii: 120 mA
Isc or Io < Imax or Ii
Pmax or Pi: 0.84 W
Po < Pi
Ci: 1 nF
Ca or Co > Ci + Ccable
Li:10 uH
La or Lo > Li + Lcable
) and current Ii(I
), and maximum power Pi(Pmax),
MAX
greater than the voltage (Uo or V
which can be delivered by the barrier.
The sum of the maximum unprotected capacitance (C
and the interconnecting wiring must be less than the capacitance (C
safely connected to the barrier.
The sum of the maximum unprotected inductance (L
the interconnecting wiring must be less than the inductance (L
connected to the barrier.
The entity parameters Uo,V
provided by the barrier manufacturer.
1/2
or V
) and current (Io or I
or I
) and the power Po
OC
t
SC
t
) for each intrinsically device
i
) which can be
a
) for each intrinsically device and
i
) which can be safely
a
or V
and Io,I
or I
, and C
and L
for barriers are
OC
t
SC
t
a
a
19