Disconnect the power supply.
1
Remove the junction box cover.
2
Connect the oven cable to the junction box
3
through the U.L.-listed conduit connector.
Connect the two black wires together with
4
twist-on connectors.
Connect the two red wires together with
5
twist-on connectors.
Connect electrical connection according to
6
local codes and ordinances.
If local codes PERMIT connecting cabinet-
grounding conductor to neutral white wire
in the junction box:
Connect the factory-crimped green and
7
white oven cable wires to the neutral (white)
wire in the junction box.
Replace the junction box cover.
8
OR
If local codes DO NOT PERMIT connecting
cabinet-grounding conductor to neutral
(white) wire in junction box:
Separate the factory-crimped green and
7
white oven cable wires.
Connect white oven cable wire to neutral
8
(white) wire in junction box.
Connect the green grounding oven cable
9
wire to a grounded wire in the junction box.
Replace the junction box cover.
10
OR
If connecting to a four-wire electrical
system:
Separate green and white oven cable wires.
7
Connect white oven cable wire to neutral
8
(white) wire in junction box.
Connect the green grounding oven cable
9
wire to the (green) grounding wire in the
junction box.
Do not connect green grounding wire to
neutral (white) wire in junction box.
Replace the junction box cover.
10
Electrical connection to junction box
3
Nameplate
red wires
white and green
grounding oven
wires - factory
crimped
red wires
green grounding
oven wires - factory
crimped
WOU-130
Max. current draw:
21 A
Max. load:
5.1 kW
WOUD-230
Max. current draw:
38.2 A
Max. load:
9.2 kW
Junction box location
for: undercounter
installation
Junction box
location for:
wall installation
cable from
power supply
box
black wires
UL - listed conduit
connector
cable from
power supply
box
white wires
black wires
UL - listed conduit
connector
5