4
VALUE MAX Bar 10
Line n.1 TRANSLATOR
Non modifiable description
Line n.2 VALUE MAXIMUM BAR XX
The maximum value of the pressure transducer must be entered. Normally in our standard groups a transducer 0-5V 0-10 bar is
used, therefore value 10 must be entered for this transducer.
MENU ACCESS
5
TOTAL YES/NO
N.1 line ACCESS MENU
Description non modifiable
N.2 line TOTAL XX
• YES: permits to access menus 8 - 9 - 10
• NO: disable access to menus 8 - 9 - 10
Menu 6 regulating of operational parameters is accessed to by pressing key (20).
2. MENU FOR REGULATING OPERATIONAL AND CALIBRATION PARAMETERS
The access to this menu is direct from configuration menu 1, otherwise proceed as follows:
check that all drawings are closed or that the water distribution network is cut. Bring the main switch to position I (ON).
While the small bell gives out some beeps, press the key,
MANUAL FUNCTION
Bar 05.0
Press key (20)
for about 2" until the following message will be displayed: appears the menu
ENTE R
PROG MENU.
6
THRESHOLD
INVERTERS
Press key (20)
ENTE R

SET POINT

Bar 05.0
M
A
6a
ENTE R
until the following message will be displayed:
GB
23