GE DEH-41267 Instrucciones De Instalación

GE DEH-41267 Instrucciones De Instalación

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

g
INDOOR TYPE
General
To comply with the National Electrical Code and Underwriters Laboratories, the
load center must be installed in accordance with the information included on the
label on the inside of the equipment. This must also be done in accordance with
applicable local electrical codes, and by a qualified electrical contractor and/or
licensed electrician.
WARNING: Hazard of electrical shock or burn. Turn off power before working
inside this equipment.
1. Remove Front :
Slip front and accessory package back into carton to protect
finish.
2. Remove Interior (optional)
Key-hole
M
Remove oblong KO
and screw (both
sides)
- Back Out Mounting Screws "M" & green ground-bonding screw "G" and save for
reuse.
- Slide Interior up to clear tabs and remove
3. Mount Box
:
- For Flush Mount, line up front box edge with finished wall surface and mount on
sides through oblong KO as shown above using screws
- For Surface Mount, screw or nail through keyhole slot and mounting holes in back of
box as shown above
TOP OR BOTTOM FEED
The load center will easily accommodate
incoming electrical service from the top
or bottom. Rotate the entire load center
enclosure if a bottom feed configuration is
required.
M
G
Mounting holes
.
PowerMark Gold ™Load Centers
4. Remove KO'S for all main and branch circuits.
First knock center KO inward. Outer rings should be alternately pried up or
driven in one at a time.
5. Pull incoming service and branch circuit wiring into box .
6. Replace interior
Reinstall mounting screws removed in Step 2.
7. Wire main, neutral, and equipment ground
Refer to rating label inside equipment for proper tightening torque. Equipment ground
is factory installed. Wire the ground and neutral as shown below.
For use as service equipment, terminate the grounding electrode to any neutral
terminal. Bond neutral to box as shown below.
Neutral
terminals
Note: For additional equipment-ground, please order Equipment-Ground kit (TGL2)
.
Equipment
Ground
terminals
AdditionalTGL2
Ground-kit
location
Bond neutral to box
using screw provided
loading

Resumen de contenidos para GE DEH-41267

  • Página 1 PowerMark Gold ™Load Centers INDOOR TYPE 4. Remove KO’S for all main and branch circuits. General To comply with the National Electrical Code and Underwriters Laboratories, the load center must be installed in accordance with the information included on the label on the inside of the equipment.
  • Página 2 Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the GE Company. General Electric Company 41 Woodford Ave, Plainville, CT 06062 DEH-41267 R01 12/12 ©...
  • Página 3 Para interiores Centros de carga PowerMark Gold ™ General Para cumplir con el Código Eléctrico Nacional (National Electrical Code) y los 4. Retire las pestañas de los orificios para el circuito principal y los secundarios Laboratorios Aseguradores (Underwriters Laboratories), el centro de carga debe instalarse de acuerdo con la información incluida en la etiqueta que se encuentra en el interior del equipo.
  • Página 4 Utilice solo interruptores de circuito de GE especificados en etiqueta de la caja a la posicion mostrada en el esquema mostrado debajo. Vuelvo a apretar los diagrama para los centros de carga.