9. COMMUNICATION

RS485 Modbus wiring diagram:
ETHERNET
RJ45
(3)
RS485 Modbus wiring diagram with Mini Web Server:
3
RS485: Required use of Belden 9842 or Belden 3106A wire (or equivalent) for a maximum bus length of 1000 m, or Category 6 wire
(1)
(FTP or UTP) for a maximum length of 50 m
120Ω terminating resistor inside the instrument (it can be set in the SETUP menu)
(2)
Ethernet: Cat. 6 (FTP/UTP)
(3)
The terminal "SG" must never be earthed
(4)
Communication tables
- The MODBUS and MBUS communication protocols are available on the
MFD4ORFCDT1 - MFD4ORFCMT" in the search field.
"
Technical data sheet: IDP000266EN_03
SXIIP
RS-485
+ – SG
2
4
SXWS10/SXWS32
RS-485
+
– SG
4
Updated: 23/09/2020
Code: MFD4ORFCDT1 - MFD4ORFCMT1
Model: NEMO D4 EC
MF..ORFCDT1
N°1
+ – SG
4
MF..ORFCDT1
N°1
+
– SG
4
http://www.imeitaly.com,
MF..ORFCDT1
N°2
+ – SG
4
MF..ORFCDT1
N°2
+
– SG
4
site, entering the codes
Created: 05/03/2020
MF..ORFCDT1
N°n
+ – SG
4
MF..ORFCDT1
N°n
+
– SG
4