Multifunction instrument with 1 input
"Easy Connect" for 3 Rogowski probes
7. GENERAL FATURES
Digital input
- The digital input allows switching the energy counting on 2 tariffs
- 2 input terminals
- Rated voltage: 12 – 24V d.c. max. 10mA
E
1 C
+
V: 27 VDC Max.
Features of the ModBus communication port:
- Programmable addresses: from 1 to 255 (5*)
- Communication speed: 4.8 – 9.6 – 19.2* – 38.4 kbps
- Parity bit: none, even*, odd
- Stop bit: 1
- Galvanically isolated with respect to the measurement inputs
- Standard RS485 3 wires, half-duplex
- Modbus® RTU protocol
- Response time (question/response time-out): ≤ 200ms
- 120Ω terminating resistor inside the instrument
(it can be set in the SETUP menu, default value: none*)
Features of the MBus communication port:
- Standard: EN 13757
- Transmission: serial asynchronous
- No. of bit: 8
- Parity bit: fixed even
- Communication speed: 300-600-1.200-2.400*-4.800-9.600bit/s
- No. of primary address: 0*...250
- No. of secondary address: 0*...99,999,999
- Load MBus:1
- Galvanically isolated with respect to the measurement inputs
- Transferred measurements: see communication protocol
* Factory setting
Diagnostic, Phase sequence correction:
In the software there is a diagnostic and correction algorithm of the
voltmetric and amperometric connection sequence.
The function can be activated on request and password protected:
it can display and modify the wiring sequence with the following
limitations:
1) The neutral conductor
(in the 4-wire connections)
positioned
(terminal 11)
2) The power factor must be between 0.9cap and 0.7ind for each
phase.
See www.imeitaly.com "TECHNICAL SUPPORT".
Technical data sheet: IDP000266EN_03
Code: MFD4ORFCDT1 - MFD4ORFCMT1
Model: NEMO D4 EC
7. GENERAL FATURES
Auxiliary supply
- Value Uaux ca: 230Vac +/-15%
- Rated frequency: 50/60Hz
- Operating frequency: 47...63Hz
- Self consumption: ≤ 2,5VA @230 Vca
Operating room temperatures:
- Min. = - 5 °C Max. = + 55 °C.
Room storage temperatures:
- Min. = - 25 °C Max. = + 70 °C
Maximum dissipated thermal power for the thermal
dimensioning of the panels:
Protection class:
- Terminal protection index against solid bodies and liquids:
IP 20 (IEC/EN 60529).
- Housing protection index against solid bodies and liquids:
IP 54 (IEC/EN 60529).
Protection of the device:
-
By means of thermal-magnetic
Room:
Housing material:
Packaged volume:
must be correctly
Updated: 23/09/2020
(terminals 20 and 21):
≤ 5W
Mechanical M1 – Electric E2
Self-extinguishing BLEND
.
3
0,70 dm
Created: 05/03/2020
4 / 6