Service Menu - Joannes VENUS BA MS 24 Instrucciones De Uso, Instalación Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Contents Description
Range
b10
Summer/Winter button opera-
0=Enabled
tion selection
1=Disabled
b11
Variable input contact opera-
0=Flowmeter exclu-
tion selection (b02=1)
sion
1=System thermo-
stat
2=Second room
therm.
Variable input contact opera-
0=Economy/Com-
tion selection (b02=2)
fort
1=Continuous Com-
fort
2=Second room
therm.
Variable input contact opera-
0=Flowmeter exclu-
tion selection (b02=3)
sion
1=System thermo-
stat
2=Second room
therm.
Variable input contact opera-
0=Economy/Com-
tion selection (b02=4)
fort
1=Continuous Com-
fort
2=Second room
therm.
b12
Not implemented (b02=4)
b13
Relay card LC32 operation
0=External gas
selection (b02=1)
valve
1=Alarm
2=System filling
solenoid valve
3=Solar 3-way valve
4=Second heating
pump
5=Alarm2
Relay card LC32 operation
0=External gas
selection (b02=2)
valve
1=Alarm
2=System filling
solenoid valve
3=Pump for
Legionella protec-
tion
4=Second heating
pump
5=Alarm2
Relay card LC32 operation
0=External gas
selection (b02=3)
valve
1=Alarm
2=System filling
solenoid valve
3=Solar 3-way valve
4=Second heating
pump
5=Alarm2
No effect on adjustment
(b02=4)
b14
Hours without DHW drawn
0-24hours
(b02=1)
No effect on adjustment
0-24hours
(b02=2)
Hours without DHW drawn
0-24hours
(b02=3)
No effect on adjustment
(b02=4)
b15
Fault 20Selection status
0=Disabled
1=Enabled
b16
Fumes Max Temperature
0-125°C
24
EN
VENUS BA
Default
MS 24
0=Enabled
0=Enabled
0=Flowmeter
exclusion
0=Economy/Com-
fort
0=Flowmeter
0=Flowmeter
exclusion
exclusion
0=Economy/Com-
fort
--
--
--
0=External gas
valve
0=External gas
valve
0=External gas
0=External gas
valve
valve
--
--
--
24hours
24hours
24hours
24hours
24hours
0=Disabled
0=Disabled
100°C
100°C
cod. 3541I710 - Rev. 00 - 06/2016
VENUS BA
Contents Description
MS 34
0=Enabled
b17
Mains Voltage Frequency
b18
Comfort burner on time
(b02=1)
Not implemented (b02=2)
Not implemented (b02=3)
Not implemented (b02=4)
b19
Flowmeter timing (b02=1)
No effect on adjustment
(b02=2)
Flowmeter timing (b02=3)
0=Flowmeter
exclusion
No effect on adjustment
(b02=4)
b20
Fan type selection
b21
Pump antiblock operation time 0-20seconds
b22
Hydraulic unit configuration
--
b23
DHW demand type selection 0=Flowmeter (450
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.

Service menu

The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu, "Hi" means History Menu: after selecting the submenu, press the Re-
set button again to access it; "rE" means History Menu Reset: see description.
"tS" - Transparent Parameters Menu
31 parameters are available, indicated by the letter "P", which are not modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.
0=External
Contents Description
gas valve
Ignition Power (b02=1)
Ignition Power (b02=2)
P01
Ignition Power (b02=3)
Ignition Power (b02=4)
P02
Heating ramp
No effect on adjustment
(b02=1)
No effect on adjustment
(b02=2)
--
P03
No effect on adjustment
(b02=3)
No effect on adjustment
(b02=4)
P04
Heating standby time
P05
Heating post-circulation
24hours
P06
Pump operation
P07
Modulating pump min. speed 0-100%
P08
Modulating pump start speed 0-100%
P09
Modulating pump max. speed 0-100%
0=Disabled
100°C
VENUS BA MS 24- 34
Range
Default
0=50Hz
0=50Hz
1=60Hz
0-40seconds
15seconds
--
--
--
--
--
--
0=Disabled
0=Disabled
1-10=seconds
0=Disabled
0=Disabled
1-10=seconds
0=Disabled
0=Disabled
1-10=seconds
0=Disabled
0=Disabled
1-10=seconds
0=Sit
0=Sit
1=Ebm NRG
2=Ebm NRV
5seconds
0=Stepper motor
0=Stepper motor
valve
valve
1=230Vac valve
0=Flowmeter (450
imp/l)
imp/l)
1=Flowmeter (700
imp/l)
Range
Default
0-100%
40%
0-100%
40%
0-100%
40%
0-100%
40%
1-10°C/minute
2°C/minute
20-80°C
35°C
20-80°C
35°C
20-80°C
35°C
20-80°C
35°C
0-10minutes
4minutes
0-255minutes
15minutes
0-7=Operation strategy
0
30%
75%
100%
VENUS BA
VENUS BA
MS 24
MS 34
0=50Hz
0=50Hz
--
--
0=Disabled
0=Disabled
2=Ebm NRV
2=Ebm NRV
5seconds
5seconds
0=Stepper
0=Stepper
motor valve
motor valve
0=Flowmeter
0=Flowmeter
(450 imp/l)
(450 imp/l)
VENUS BA
VENUS BA
MS 24
MS 34
40%
40%
2°C/minute
2°C/minute
35°C
35°C
4minutes
4minutes
15minutes
15minutes
4
4
30%
30%
75%
75%
100%
100%