1 MiniCO Control Panel description

Conventional Control panel with diffusion sensor of carbon monoxide (CO) and nitrogen dioxide
(NO
) UNE 23300 certified.
2
This control panel provides the MCO110, MCO120 and MCO120DVB references with 10 and
20 sensors respectively.
They are particularly suitable for parking or areas that need only 1 ventilation zone or
installation of a few sensors in it.
.
The control panel displays the maximum concentration of CO in the detection zone, activating
the ventilation and alarm when a specific concentration is reached after expiry of the set delay.
It has dry contact outputs for ventilation and a 24 Vdc alarm output.
The system works with CO sensor ("SCO" reference) and NO
same area.
NO
sensors transform measures of NO
2
shown it in the display as a single concentration of CO, activating the ventilation and alarm
when established CO levels are reached.
The control panel allows manual activation and deactivation of ventilation.
The equipment is designed for using diffusion sensors calibrated at factory for operation
throughout the operational life of their sensors, and UNE 23300 certified.
Technical characteristics:
Control panel of 1 ventilation zone with diffusion sensor brand COsensor model SCO (CO
sensor) and SDN
Dry contact output (COM / NA) for ventilation 1 and ventilation 2 (DVB model only).
Alarm output 24 Vdc 0.8 A.
Space for 2x12 Vdc 2 Ah batteries (DVB model only)
Display 3-digit, 7-segment.
Dimensions: 280 x 225 x 105 mm.
UNE 23300 certified.
TECHNICAL SPECIFICATIONS
Power supply
Maximum consumption
Bateries (Only DVB model)
Power supply fuse
Sensors by zone
IP
Dry contact ventilation
Alarm output current
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
COsensor Control Panel
MCO110 / MCO120 / MCO120DVB
concentration in an equivalent measure of CO, and
2
(NO
sensor).
2
230V 50-60Hz/AC
Alarm output fuse
20 VA, 230 Vac
Zone output voltage
2 x 12 Vdc 2 Ah SLA
Zone fuse
4 A
Ambiental conditions
10 SCO/SDN(MCO110)
Dimentions
20 SCO/SDN(MCO120)
30
Weight (without batteries)
230 Vac / 30 Vdc 2A
Standard
0,8 A, 22 Vdc
CO measuring range
Time between measures at te
zone
FABRICANTS DE PRODUITS CONTRE INCENDIES
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
sensors ("SDN" reference) in the
2
Reseteable
26 Vdc
2 A
-10ºC +50ºC
208 x 225 x 105 mm
3,45 Kg
23300
0 - 300 ppm