2 Control Panel

2.1

Indication leds

CENTRAL EN SERVICIO
MAINS ON
ALARMA
ALARM
VENTILACIÓN
VENTILATION
NIVEL VENTILACIÓN
VENTILATION LEVEL
AVERÍA DE ZONA
ZONE FAULT
UNE 23300
V0-604005
A
Green LED: System operating normal.
B
Red LED: Indicates Alarm Relay activation.
C
Green LED: Indicates Ventilation Relay activated.
Amber LED: Indicates that Ventilation Level has been exceed.
D
E
Amber LED: Indicates fault or trouble on detection zone.
F
Green LED: Indicates that display is showing a CO concentration (ppm).
G
Green LED: Indicates that display is showing the Ventilation Level.
Green LED: Indicates that display is showing the Ventilation Delay (temporization).
H
2.2

External controls

1. Selección Display:
2 & 3.
:
4. ON/OFF Ventilation
10
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
COsensor Control Panel
MCO110 / MCO120 / MCO120DVB
A
3
B
C
D
E
4
To select the information shown in the display: CO
Concentration, Ventilation Level or Ventilation Delay.
To increase (
) or decrease (
To activate/deactivate on manual mode the ventilation at any
moment.
FABRICANTS DE PRODUITS CONTRE INCENDIES
ppm CO
F
NIVEL
G
LEVEL
TEMPORIZACIÓN
H
2
TIMING
1
DISPLAY
VENTILACIÓN MANUAL
MANUAL VENTILATION
) the numerical parameters.