ACCESS TO PARAMETER CONFIGURATION
PROCEDURE
 S witch the thermostat off
 P ush the
keys at the same time.
 U se keys
to modify the display value up to the
password value "10", and press
will have access to the parameters.
value of selected
parameter
selected
parameter: P..
 U se keys
to scroll the various parameters (see
"Parameter list" described above).
 P ress
to confirm the parameter change (the value will
start flashing).
 U se keys
to change the value.
 P ress
to save the new value setting or
the modification.
 A fter completing the modification of the parameters
concerned press key
N.B.: the parameter configuration phase is of limited duration.
Once a certain time has elapsed (around 2 minutes) the
thermostat will switch back into the Off status and only
the saved changes will be retained.
FWEC3
Advanced plus electronic controller
FC66002765
.
. If it is correct, you
selected parameter
description
selected parameter
description
to cancel
to exit the procedure.
AVAILABLE CONFIGURATIONS (PARAMETER P00)
The LCD controller can be configured in various ways according
to the type of system. Various configurations can be obtained
through the P00 parameter (see configuration procedure of
controller parameters).
001
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: LOCAL
002
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: REMOTE
003
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: WATER
004
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: LOCAL
005
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: REMOTE
006
 S ystem pipes: 2
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: WATER
007
 S ystem pipes: 2
 V alve: NO
 H eating element: YES
 S peeds: 3
 S ummer/winter switching logic: LOCAL
008
 S ystem pipes: 2
 V alve: NO
 H eating element: YES
 S peeds: 3
 S ummer/winter switching logic: REMOTE