Installation notes:
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada
and National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable
ends.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure
according to the regulations in the CEC for Canada or NEC for USA.
Install in pollution degree 2 or better.
Substitution of components may impair the suitability for division 2 / zone 2 installation.
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and
do not separate connectors when energized and an explosive gas mixture is present.
WARNING: Do not install or remove modules from the Power Rail and do not remove connectors
from the module unless Area is known to be Non Hazardous.