Model 6335C, 6335D
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G
Class I, Zone 0, IIC
Ambient temperature limits
T6: -40 to + 60 deg. Celcius
Terminal 41,42,43,44
Vt or Uo: 9,6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Terminal 51,52,53,54
Vt or Uo: 9,6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes
stipulated in The National Electrical Code (ANSI-NFPA 70).
When installed in Class II locations the Transmitter shall be installed in an enclosure
with a specified ingress protections of IP6X according to IEC60529 and Dust-tight
conduit seals must be used.
Equipment that is FM-approved for intrinsic safety may be connected to barriers
based on the ENTITY CONCEPT. This concept permits interconnection of approved
transmitters, meters and other devices in combinations which have not been
specifically examined by FM, provided that the agency's criteria are met. The
combination is then intrinsically safe, if the entity concept is acceptable to the
authority having jurisdiction over the installation.
The entity concept criteria are as follows:
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(V
which the device can receive and remain intrinsically safe, must be equal to or
6335QF01revAC.doc
Installation Drawing 6335QF01
S
E
N
S
O
R
Ch 1
S
E
N
S
O
R
Ch 2
) and current Ii(I
MAX
2005-12-16
Non Hazardous Location
Terminal 11, 14
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
+
-
+
-
Terminal 21, 24
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
), and maximum power Pi(Pmax),
MAX
Um < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
Associated Apparatus
or Barrier
with
entity Parameters:
Associated Apparatus
or Barrier
with
entity Parameters:
Um < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable