Error Messages And Warnings During Setup; Error Messages And Warnings During Operation - BONFIGLIOLI Vectron Agile AGL202 Guia De Inicio Rapido

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Error messages and warnings during setup

Error messages
Fault clearance
Check rated motor values in parameters 370...376. Correct the values if
...
SF001
SF022
necessary. Repeat Setup. Check motor cable connections and frequency inverter
connections.
Warnings
Check rated motor values in parameters . Correct the values if
...
SA001
SA004
necessary. Repeat Setup.
SA021 , SA022
The following causes are possible: The motor cable cros- section is not sufficient.
The motor cable is too long. The motor cable is not connected correctly.
,
SA041 SA042
Check P372 (rated speed), P375 (rated frequency).
The machine data for star connection is entered, but the motor is connected in
SA051
delta. For star connection change the motor cable connection. For delta connec-
tion check the entered rated motor values. Repeat Setup.
The machine data for delta connection is entered, but the motor is connected in
SA052
star. For delta connection change the motor cable connection. For star connection
check the entered rated motor values. Repeat Setup.
Check motor connection and frequency inverter connections.
SA053
- Press ESC to correct a parameter value after an error message or after a warning message.
- Press ENT to ignore a warning message. Setup is continued. It is recommended to check
the entered data.

Error messages and warnings during operation

Error messages
Fault clearance
,
F0102 F0103
Frequency inverter overloaded. Check load behavior. Check motor parameter
settings.
Overtemperature. Check cooling, fan, sensor and ambient temperature.
Low temperature. Check ambient temperature and electrical cabinet heating.
,
F0400 F0403
Motor temperature too high or sensor defective. Check connection on X.12.4.
Phase failure. Check motor and wiring.
Overloaded, short circuit or earth fault, motor current or phase failure. Check load
...
F0500
F0507
behavior and ramps (P420 ... P423). Check motor and wiring.
DC link voltage too high or too low. Check deceleration ramps (P421, P423) and
...
F0700
F0706
the connected brake resistor. Check mains voltage.
Power failure or phase failure, voltage brake- chopper or motor chopper too high.
Check mains voltage, mains fuses and circuit.
,
F0801 F0804
Electronic voltage (DC 24V) too high or too low. Check wiring of control terminals.
Maximum frequency achieved. Check control signals an settings.
...
F1100
F1110
Check deceleration ramps P421, P423) and the connected brake resistor.
...
Internal STO-error.
F1201
F1204
F1205
Enable signals STOA and STOB were not actuated at the same time, but with a
time offset bigger than 5 seconds. Check the circuitry of the enable input signals.
...
F1206
F1209
Internal STO-error.
Minimum output current. Check motor and wiring.
F1310
F1401
Reference value signal on input X12.3 faulty, check signal.
F1407
Overcurrent on input X12.3, check signal.
Overcurrent on input X12.4, check signal.
F1408
05/2013
Please use the instruction manual for details.
Please use the instruction manual for details.
39
Agile
Quick Start Guide
Tabla de contenido
loading

Este manual también es adecuado para:

Vectron agile agl402

Tabla de contenido