FireClass
Type Identification
Value:
System Compatibility:
Environment:
Operating Temperature:
Storage Temperature:
Operating Humidity:
Dimensions (HxWxD):
Mounting Require-
ments:
Recommended Wire
Size:
Maximum Wiring
Resistance
Monitored Circuit:
Battery Requirements:
Standby:
Alarm - without remote
LED:
Alarm - with remote LED:
Addressable Device Conditions:
- Normal
- Active
- Short Circuit wiring fault
- Open Circuit wiring fault
- Device Type Invalid
- Device No Response
Electromagnetic Compatibility
The FC410MIM complies with the following:
Product family standard EN50130-4 in
respect of Conducted Disturbances, Radiated
Fixing Instructions Doc. version 5.0
ENGLISH
128
Use with FC Fire
Alarm Controllers
Indoor
Application only
-25 °C to +70 °C
-40 °C to +80 °C
Up to 95% non-
condensing
57 x 48 x 13 mm
Any suitable elec-
trical enclosure
2
Min. 1.5mm
2
Max. 2.5mm
10 Ohm
0.46 mA
0.46 mA
4.5 mA
Immunity, Electrostatic Discharge, Fast Tran-
sients and Slow High Energy;
EN61000-6-3 for emissions.
Introduction
The FC410MIM Mini Input module is designed
to monitor fire contacts, such as extinguishing
system control, ventilation control, fire door con-
trol etc. The module provides one identifiable
detection spur which is capable of monitoring
multiple normally open contacts or a single nor-
mally closed contact.
The FC410MIM can be mounted in any electrical
enclosure with sufficient depth to accommodate
FC410MIM and the contacts monitored by the
IN+ and IN- terminals, ie, no field wiring.The
remote LED (if required, not supplied) must be
located within the same electrical enclosure.
Features
FC410MIM monitors the following types of con-
tacts:
multiple normally open contacts;
single normally closed contacts.
FC410MIM identifies and communicates the
status of monitored contacts and wiring to the
FireClass Fire Controller. FC410MIM contains an
output for an external LED (not supplied). As a
status indicator, the LED lights when the moni-
tored contact (normally off) switches to an active
state.
Wiring & installation notes
The following notes apply:
1 There are no user-required settings(switches,
headers) on the FC410MIM.
2 All wiring must conform to the applicable
standards. All conductors to be free of earths.
3 Mount the FC410MIM within a suitable elec-
trical enclosure.
4 Connect the wiring for the monitored contact
as shown in Fig. 3.
5 Verify the correct polarity of wiring before
connecting the FC410MIM to the addressa-
ble loop circuit.
FC410MIM
3/12