ENG
Check that the electrical box cover of the thermostat or the electronic controller is properly
•
installed.
Check that components that might have been replaced during servicing are original.
•
3.
Refrigeration system:
Check that the compressor is functioning properly.
•
Check the starting relay, the overload and the capacitor. The Supplier recommends that the
•
compressor's starting relays and overloads be replaced every 3-4 years.
Check the fan motor condenser and fan motor evaporator.
•
Check that the thermostat or the electronic controller and its components are functioning properly.
•
Check the cooling performance of the ICM.
•
Check the cooling circuit using the appropriate leak detector in case there is any concern or sign
•
of refrigerant leak.
The Supplier recommends that the compressor's starting relays and overloads be replaced every
3-4 years.
Do not damage the refrigerant circuit.
1.
Avoid damages resulting from improper installation & operation, improper maintenance &
cleaning, as well as improper handling and transportation, as per paragraphs 3, 5 and the
Appendix A above.
2.
Do not perform unauthorised adaptations, modifications or adjustments to the cabinet.
18
GUIDELINES TO PREVENT CORROSION OF THE CABINET
APPENDIX C