Model
Part no.
Nominal input voltage
Input range, full output specifications
Input range, three step charger mode
Input range, no defects
Low voltage set point to trigger alarm *
Delay lower input set point *
Recommended fuse input
Wire size < 3m
Wire size > 3m
Output
Voltage adjustable *
Nominal voltage stabilized voltage *
Output voltage 3 step charger
Absorption / Float
Output voltage dimmer
Stabilized
Ripple
Maximum power
Rated power
Current max. (derating >40°C, 5%/°C)
Maximum 3 step charge current (bulk)
Wire size < 2m
General
Ambient operating temperature
Storage temperature
Operating humidity
Galvanic isolation
Current limited
Three stage battery charge option
Efficiency
No load consumption
Protections
Over current
Over heat
Options
3 Step battery Charger
Dimmer function
Alarm contact
Communication
Parallel connectability
Mechanical
Connections input/output
Dimensions (HxWxD)
Mounting holes
Weight
Cabinet
Directives and standards:
Setpoints software
Low input voltage switch off level
Low input voltage switch off delay
Low input voltage switch on level
High input voltage switch off level
High input voltage switch on level
Output voltage
* Adjustable by means of MasterAdjust software, see www. mastervolt.com
SPECIFICATIONS MAGIC
MAGIC 24/12-20A
MAGIC 24/24-20A
81300100
81300200
24V
24V
19-32V DC
19-32V DC
24-32V DC
24-32V DC
0-35V DC
0-35V DC
20.0V DC
20.0V DC
30 sec.
30 sec.
15A-T
30A-T
4mm²/AWG11
6mm²/AWG9
6mm²/AWG9
10mm²/AWG7
10-15V DC
20-28.5V DC
13.6V DC
27.2V DC
14.25 / 13.25V DC
28.5 / 26.5V DC
4.0-13.0V DC
8.0-26.0V DC
2% at extremes of temperature, load and input
Max 1% peak peak
300W @ U
=12.0V
580W @ U
out
300W @ U
=12.0V
580W @ U
out
20A
20A
16A
16A
6mm²/AWG9
6mm²/AWG9
Guaranteed operation: 0°C to 60°C (derating above +40°C, 5% per °C); in practice: -20°C to 60°C/
guaranteed operation: 32 °F to 140 °F (derating above 104 °F, 3% per °F), in practice -4°F to 140 °F
-25°C to 85°C/ -13 °F to 185 °F
95% max., non-condensing
Yes
Yes, I-max
Yes (DIP switch setting).
90% (at nominal input voltage, full load) typical; 92% peak
Typical <115mA
Limited by current sensing circuit
Limited power by temperature sense circuit
Yes, all models, by means of DIP switch settings
Yes, by external momentary switch via fast-on connection. To be activated by DIP-switch setting
Yes (fast-on connector)
Quasi RS232, modular RJ12 connection, to alter set points and to change characteristics. Optional:
MasterBus serial interface (art. no. 77030450) to control & configure from MasterBus network.
In mode Stabilized Voltage, up to 6 devices in parallel
Screw terminals, maximum wire size 16mm² / AWG 5
227 x 154 x 81 mm [8.9 x 6.1 x 3.2 inch]
Diameter 5mm
1.8 kg / 3.9 lbs
Anodized aluminium, strapton ABS blend, blue RAL 5021
-
EMC directive 2004/108/EC
-
Transient voltage protection: meets ISO 7637-2
-
Electrostatic voltage protection: meets ISO10605, 14892, 8kV contact, 15kV discharge
-
RoHS directive 2011/65/EC
Default setting
10.0V / 20.0V; three step charger mode:12.0VDC / 24.0VDC.
30 seconds
11.0V / 22.0V; three step charger mode: 13.0VDC / 26.0VDC.
16.0V / 32.0V
15.0V / 30.0V
13.6V / 27.2V
MAGIC 12/12-20A
81300400
12V
11-16V DC
12-16V DC
0-17.5V DC
10.0V DC
30 sec.
30A-T
6mm²/AWG9
10mm²/AWG7
10-15V DC
13.6V DC
14.25 / 13.25V DC
4.0-13.0V DC
=24.0V
300W @ U
out
out
=24.0V
300W @ U
out
out
20A
16A
6mm²/AWG9
MAGIC 12/24-10A
81300300
12V
11-16V DC
12-16V DC
0-17.5V DC
10.0V DC
30 sec.
30A-T
6mm²/AWG9
10mm²/AWG7
20-28.5V DC
27.2V DC
28.5 / 26.5V DC
8.0-26.0V DC
=12.0V
300W @ U
=24.0V
out
=12.0V
300W @ U
=24.0V
out
10A
8A
4mm²/AWG11
loading

Este manual también es adecuado para:

Magic 12/24-10Magic 24/12-20Magic 24/24-20