Maintenance; Strobe Flashtube Replacement; Alarm System Maintenance; Remote Sensing Option - Bradley S19-320EXP120 Manual Del Usuario

Ocultar thumbs Ver también para S19-320EXP120:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation

Maintenance

Troubleshooting
1. If the alarm (horn and strobelight) does not operate when water flows:
• Check that the circuit breaker or fuse is supplying power to the alarm.
• Check that the direction of water flow corresponds to the arrow on the flow switch body.
• Check that water flow is sufficient (2.5 gallons per minute is required).
• Check all electrical connections, including the power supply and the waterproof cable from the flow
switch to the alarm.

Strobe flashtube replacement

1. Loosen the locking band and remove the clear plastic dust cover from the top of the strobelight.
2. Loosen (but do not remove) the three screws holding the amber dome in place. Rotate the dome
slightly clockwise and remove the dome.
3. Remove the flashtube assembly by simply unplugging it from the top of the strobelight.
4. Replace the flashtube assembly with a new one.
NOTE: Avoid touching the flashtube glass with your fingers. Be sure the flashtube assembly is firmly plugged
into the socket.
5. Reattach and tighten the amber dome.
6. Reattach and tighten the clear dust cover.
7. Test the alarm as described in Step 5 "Test the alarm system" on page 5.

Alarm system maintenance

1. The Bradley Alarm System is designed to be virtually maintenance free. An occasional damp cloth
wiping of the clear dust cover is all that is needed to ensure maximum visual attention-getting ability.

Remote Sensing Option

If remote sensing is wanted, remove the pipe plug from the side of the junction box. Connect the extra
black wire (common to both switch arrangements) and the blue wire (normally open switch
arrangement) or red wire (normally closed switch arrangement) to your application per local electrical
codes. The switch is rated at 5 amps at 120 and 220/240 volts. Your connection should be water tight.
Bradley Corporation • 215-1083 Rev. F; EN 07-511