Fault code
Fault
Overtemperature protec-
F09
tion intervention
Flow sensor fault
F10
Return sensor fault
F11
Gas valve connection
A11
DHW sensor fault
F12
Fume probe fault
F13
Fume extraction duct
A14
safety device intervention
Supply voltage under
F34
180V
Wrong supply frequency
F35
A23-A24-A26-
Water pressure switch
F20
fault
F21-F40-F47-
F51
Incorrect system water
F37
pressure
External probe fault
F39
Card parameter fault
F19
Limit thermostat fault with
F50 - F53
parameter b06 = 1 or 4
Maximum number of con-
secutive Resets excee-
F64
ded
Calibration required
F62
Specific combustion con-
A88
trol errors or gas valve
344
BlueHelix HiTech RRT C
Possible cause
Flow sensor damaged
No water circulation in the
system
Air in the system
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Damaged electrical con-
nection between the con-
trol unit and gas valve
Sensor damaged
Wiring shorted
Wiring disconnected
Probe damaged
Wiring shorted
Wiring disconnected
Fault A07 generated 3
times in the last 24 hours
Electric mains trouble
Electric mains trouble
Wrongly configured para-
meter
System pressure problems
(transducer)
b06 set to 3
Pressure too low
Water pressure switch
damaged or disconnected
Probe damaged or wiring
shorted
Probe disconnected after
activating the sliding tem-
perature
Wrong card parameter set-
ting
No/poor water circulation
in the system
Air in the system
Incorrect parameter
Maximum number of con-
secutive Resets exceeded
New card or boiler not yet
calibrated
Calibration activation with
burner lit.
Combustion problem,
faulty gas valve or PCB
cod. 3541V300 - Rev. 00 - 02/2021
Cure
Check correct positioning and opera-
tion of the flow sensor and replace it if
necessary
Check the circulating pump and hea-
ting system
Vent the system
Check the wiring or replace the sensor
Check the wiring or replace the sensor
check the wiring, or replace the valve
Check the wiring or replace the sensor
Check the wiring or replace the fume
probe
See fault A07
Check the electrical system
Check the electrical system
Check if parameter b04 is configured
correctly (default 0=pressure switch)
System pressure value outside set
limits (transducer)
Fill the system
Check the water pressure switch
Check the wiring or replace the sensor
Reconnect the external probe or disa-
ble the sliding temperature
Check and if necessary modify para-
meter b15 to 3
Check the circulating pump and hea-
ting system
Vent the system
Check the correct parameter setting
Disconnect the power supply to the
boiler for 60 seconds and then reins-
tate the boiler
Do complete manual calibration
Reset the fault and do complete
manual calibration.
If necessary, replace the gas valve or
PCB.