PanelView 550/600 Touch Screen Terminals
This document describes how to mount a PanelView 550/600 touch screen
terminal in a panel or enclosure and apply power.
• hazardous locations
• European Union Directive Compliance
• wiring and safety guidelines
• enclosures
• required tools
• mounting dimensions
• clearances
• installing the terminal in a panel
• installing the memory card retainer
• connecting DC power
For more information on the PanelView 550/600 Operator Terminals, refer to
Publication 2711-6.1.
Hazardous Locations
See nameplate label on terminal for certification details.
ATTENTION: In Class 1, Div 2 and Class 1, Zone 2 hazardous locations,
!
the PanelView 550/600 terminal must be wired per the National Electric
Code and/or Canadian Electric Code as it applies to hazardous locations.
Peripheral equipment must also be suitable for the location in which it is
installed.
The PanelView 550 touch screen terminals have an operating temperature code of
T2 (maximum operating temperature of 300 ° C or 572 ° F). Do not install the
terminals in environments where atmospheric gases have ignition temperatures
less than 300 ° C (572 ° F).
The PanelView 600 touch screen terminals have an operating temperature code of
T4 (maximum operating temperature of 135 ° C or 275 ° F). Do not install the
terminals in environments where atmospheric gases have ignition temperatures
less than 135 ° C (275 ° F).
Installation Instructions
41061-109-01(B)