Air Pressure Switch - Rendamax R3 EVO Serie Manual De Uso E Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Commissioning

Air pressure switch

3
Check water flow
The water flow through the boiler can
be checked with two different methods
shown below.
∆T measurement
Check the temperature difference over
the boiler (∆T flow-return) when the
boiler is running on 100% load.
To ensure correct operation of the boiler,
the ∆T should not exceed the max. ∆T
as indicated in the technical data.
An indication of the actual flow rate can
be found with the following calculation:
∆p measurement
Check the pressure difference over
the boiler (∆p flow-return) when the
boiler pump is running (burner on is not
required). The nominal Δp for each
boiler type can be found in the Technical
data.
An indication of the actual flow rate can
be found with the following calculation:
38
Adjustment Air pressure switch
Connect a pressure gauge to the
indicated measuring points on the
Start the boiler to minimum
switch (3).
load (0%).
Measure the pressure
differential across the switch during the
start up. The measured pressure should
be 0,8 mbar or higher.
To set the pressure turn the dial on the
switch (4).
The difference between the measured
pressure and the set pressure should
be minimum 0,4 mbar.
4
q
= (∆T
actual
q
= √(∆p
actual
/ ∆T
) * q
nominal
measured
nominal
/ ∆p
) * q
measured
nominal
nominal
[m
/h]
3
[m
/h]
3