cal and physical features and thus a constant level of sensitivity.
It is therfore strongly recommended to make sure that this conditioning
period has passed before carrying out any checks on the activation
level.
NOTE: Short power failures have no effect.
The built-in siren are activted intermittently after a delay time of about 5
seconds from the switching on of the red led signalling that the threshold
has been exceeded, as mentioned above.
After another 20 seconds, the relay output is activated the (the 20s
delay allows the user to ventilate the room to prevent the solenoid valve
from triggering, in the case of a false alarm).
If the concentration of gas falls below the activation lavel, during this
time span, the signal is cancelled and the above-mentioned delay time is
reset. The gas detector is provided with a terminal board which is acces-
sible for connection into the circuit by removing the cover.
Terminals 1 and 2 are for the supply volatage - 230 Vac – while termi-
nals 3, 4 and 5 are the relay contacts – NO, C, NC -

TECHNICAL DATA

– Rated voltage: 230V – 50 Hz
– Range: 0,85 Vn to 1,1 Vn
– Current demand: 6VA approx. At 230 Vac
– Operating ambient temperature
• reference= 20° C ± 5°C
• range = -5°C to + 40°C
– Operating ambient Relative Humidity:
• reference= 65% ±10% at 20°C ±5°C
• range = 30% to 90%
– Output relay:
– Degree of protection: IP67
– Changeover contact
– Terminal 3: normally open contact (NO)
– Terminal 4: common wire
– Terminal 5: Normally closed contact (NC)
– Contact capacity: 8A/250Vac-cosϕ 1 ; 5A/250Vac- cosϕ 0,4
– Acoustic radiation pressure: 85 dbA at 3m
– Activation threshold: factory-set.
– 6000ppM ± 1000ppM Methane/air ratio (equal to 12% of the
Lowest Explosion Limit (LEL of methane).
– Limits of variation of the threshold:
– 2500ppM to 9250ppM (equal to 5% and 18,5% of the LEL of methane).
– Time of the sensor's reactivation in the case of short power failures:
– to switch on the acoustic signal: 5 sec. ± 5%
– to activate the relay output: 25 sec. ± 5%.
– Stabilization period of the activation threshold after more than 2
weeks without power: 7 days
– Enclosure:
– indoor-type, for fixed wall-mounting by means of screws.
– Degree of protection IP 42
– dimensions 156 mm x 90,5 mm x 40,5mm
– distance between centers, reachable after removing the front part by
using a tool; 60 mm and 83,5 mm
– Weight: 330 grams
Standard reference
UNI-CEI-70028
INSTALLATION
Assembly
The detector is installed directly on the wall, with power supply cables
and/or controls carried by surface raceways, which lead to the stan-
dard round or three-component rectangular boxes onto which the detec-
tor can be easily fitted using the drilling hoses provided.
Fixing holes
In order to reach the fixing holes, the cover of the detector must be remo-
ved by using the point of a screwdriver in the appropriate slot in the
slide. In order to reach the terminals and one of the fixing holes, the ter-
minals' cover must be removed by undoing the fixing screws.
60 mm
82,5 mm