Wiring Diagram A: 100-277 V~ GRX-TVI — 1 Distribution Panel - 1 Feed
L2/H2 is internally shorted and
is the Line/Hot feed that powers
the internal circuitry of the
GRX-TVI. Use any voltage in the
range of 100-277 V~. Refer to
the Note at the bottom of
Page 1.
Control Unit /
Dimmed Line/
Dimmed Hot, DL / DH
Dimmer *
Neutral
Line/Hot
Use 20 A (10 A CE)
Distribution
maximum circuit
Panel
breaker/MCB
Line/Mains Voltage:
100 - 277 V~
Wiring Diagram B: 100-277 V~ GRX-TVI — 2 Distribution Panels - 2 Feeds
L2/H2 is internally shorted and
is the Line/Hot feed that powers
the internal circuitry of the
GRX-TVI. Use any voltage in the
range of 100-277 V~. Refer to
the Note at the bottom of
Page 1.
Dimmed Line/
Control Unit /
Dimmed Hot, DL / DH
Dimmer *
Neutral
Line/Hot
Line/Hot
Use 20 A (10 A CE)
Distribution
Neutral
maximum circuit
Panel A
Earth/Ground
breaker/MCB
Line/Hot
Distribution
Neutral
Panel B
Earth/Ground
Line/Mains Voltage:
100 - 277 V~
GRX-TVI
220-
100-
240 V~
120 V~
EARTH/GROUND
CONNECTIONS
Line/Hot
Neutral
Neutral
Earth/Ground
GRX-TVI
EARTH/GROUND
CONNECTIONS
L1/H1 is the Line/Hot feed that
powers the Switched Line/Hot
output to the load shown here as
the same voltage as L2/H2.
NOTICE: 0-10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Switched Line/Hot
Neutral
To additional ballasts/drivers
Note: Load must provide a
0-10 V- source only!
* For dimmers with SH
(Switched Hot) terminal,
please cap off "SH"
L1/H1 is the Line/Hot feed that
powers the Switched Line/Hot
output to the load. Use any voltage
in the range of 100 - 277 V~.
NOTICE: 0-10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Switched Line/Hot
Neutral
To additional ballasts/drivers
Note: Load must provide a
0-10 V- source only!
* For dimmers with SH
(Switched Hot) terminal,
please cap off "SH"
3
0-10 V- Ballast/Driver
Earth/Ground
0-10 V- Ballast/Driver
Earth/Ground
0-10 V- Ballast/Driver
Earth/Ground
0-10 V- Ballast/Driver
Earth/Ground
www.lutron.com