Calorex DH30 Serie Instrucciones De Instalación página 5

Ocultar thumbs Ver también para DH30 Serie:
Idiomas disponibles
  • ES

Idiomas disponibles

MODEL DH60AHP ( R134a ) HIGH TEMPERATURE MACHINE
As the Heat Pump contains electrical and rotational equipment, it is recommended that ONLY competent persons carry out any work on this type of machine
(see guarantee). Isolate electrically before entering machine or removing panels.
INSTALLATION - MODEL 60AHP (134a)
1. Remove machine from packaging and locate fixing bracket.
D
A
B
C
2. Locate bracket on wall in required position. Drill hole Ø 6.0mm
(no. 10) by 60mm deep as shown at 'A'. Insert wall plug and
screw bracket in place.
3. Set bracket level with spirit level 'D' as shown, drill through and
fix it at 'B'
with wall plug and screw.
4. Ensure bracket still level, tighten screws 'A' and 'B', finally drill
and fix as above
at position(s) 'C'.
5. Check all screws are tight.
6. Lift dehumidifier on to locating lugs on wall bracket.
7. Remove front cover as shown FIG 1.
FIG 1
HINGE AND LIFT
COVER AWAY
REMOVE COVER
FIXING SCREWS
8. Electrical supply to the unit must be sized according to data
on serial number label paying special attention to I.E.E.
regulations latest edition regarding the special conditions
governing electrical supply to machines in potentially damp
areas. The machine should be installed in accordance with
EMC2004/108/EC.
9. The electrical supply should be connected to the terminal
block mounted on the side of the bracket supporting the
compressor. Brown/red to 'live', blue/black to neutral and earth to
the stud provided.
10. The fan mode switch is permanently wired to give continious
run.
11. Locate pipe from drip tray and run it away to waste. A short
length of 10mm pipe is provided which should be led into a fixed
waste pipe. Two pipe outlet holes are provided, one to rear of
unit, one below the unit.
INSTALLATION INSTRUCTIONS
HEALTH & SAFETY WARNING
R
12v REMOTE HUMIDISTAT & THERMOSTAT
CONNECTIONS
12. A remote humidistat and thermostat are required in order for the
machine to operate fully.
13. Connect the humidistat and thermostat as shown below.
N
L
Humidistat or
Air stat (not
supplied)
250M MAX
1mm SQ CABLE
RESISTANCE HEATER
14. Ensure safety thermostats shown below are set, ie push red buttons.
FIG 2
HINGE AND LIFT
COVER AWAY
REMOVE COVER FIXING SCREWS
Remove cover to gain access to manual reset thermostat.
19. Replace front cover, turn on electrical supply and turn humidistat
towards 'max', unit fan will start, followed 6 minutes later by the
compressor.
GAS CHARGE
The dehumidifier incorporates a hermetically sealed refrigeration circuit
containing less than 6kg of refrigerant. R134a Global warming potential
(GWP) 1300.
1
GREEN/YELLOW
2
BLUE
WHITE
3
BROWN
BROWN
4
ORANGE
5
PINK
6
RED/BLUE
Remote Control
Interface
Safety thermostat
press to reset
(red button)
loading

Este manual también es adecuado para:

Dh35 serieDh50 serieDh55 serieDh60 serieDh60ahp