220-240V/CE Control Interface

Important Installation Information

Install in accordance with all national and local electrical codes.
Check for short circuited loads during new installations before wiring the GRX-TVI.
Caution:
Multiple feeds may enter this enclosure. Locate and lock each feed circuit breaker/MCB in the OFF position
before wiring the Interface.
Proper short circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A for CE)
maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC 898/EN60898 is recommended) with adequate
short circuit breaking capacity for your installation.
Terminal blocks are rated for two #12-22 AWG (0.5-2.5 mm
Strip 3/8 in. (10 mm) of insulation from wires.
Wiring Diagram A shows a GRX-TVI wired from one distribution panel. If the
power requirement of the complete system is less than an MCB/circuit
breaker rating, one feed can be jumpered inside the enclosure (as shown).
Wiring Diagram B shows a GRX-TVI wired from two separate distribution panels that may be different phases or voltages.
Use the internal terminal block label to see where to land wires.
— The label shows two separate Hot/Live terminals (L
L
/H
is the Hot/Live feed to power the lighting load.
1
1
L
/H
is the Hot/Live feed that powers internal circuitry of the GRX-
2
2
TVI.
L
/H
has a 100-127V connection and a 220-240V connection - use
2
2
only the one corresponding to line voltage for your application.
Note 1:
Not all terminal blocks receive a connection.
Note 2:
The power feed to the Control Unit and L
TVI must be the same phase!
Class 2/PELV, 0-10V wiring from a ballast to the GRX-TVI-
CE must be separated from the power wiring. Enter the
Class 2/PELV wires through the knockout adjacent to the 0-10V terminal blocks. The Nomex
separation and is flexible to allow access to the terminals. The barrier must be in place when installation is
complete.
GRX-TVI Internal Terminal Block Label Definitions
Use only one input according to Input Voltage:
L
/H
240V
Power input for GRX-TVI control (line/mains voltage must be 220-240V)
2
2
L
/H
127V
Power input for GRX-TVI control (line/mains voltage must be 100-127V)
2
2
N2
Neutral for GRX-TVI control
DL
/DH
GRAFIK Eye 3000 Series Control Unit Lighting Zone connection (Phase Control Input to GRX-TVI)
2
L
/H
Power input for lighting load
1
1
N
Neutral for lighting load (2 terminals provided and internally tied together — one for input neutral and one
1
for load neutral)
SL
/SH
Switched output to power lighting load
1
1
+ -
0-10V control signal wires (ballast must provide a 0-10V source only)
2
2
) wires per terminal.
/H
& L
/H
).
1
1
2
2
Use only if
your
line/mains
voltage is
220-240V.
/H
of the GRX-
2
2
10mm
(3/8in.)
Input from distribution
panel.
Use only if your line/mains voltage is
120-127V.
barrier ensures
®