6 HEATING CIRCUIT 1 / 2

(Available with all systems (1 - 18)
Circulation Pump
Mixing Valve +
Mixing Valve -
Water flow Temperature
Outdoor Temperature
Room Thermostat
Parameters
Active
Heating Curve
Outside temperature
Water flow temperatures
Room Thermostat for adjusting the
supply temperature (heating
circuit)
Day Correction Start
Day Correction Stop
Day Correction
Night Correction Start
Night Correction Stop
Night Correction
Summer operation
Mixing Valve cycle time
Max Flow Temperature
Domestic Hot water priority
(tank 1)
Domestic Hot water tank backup heater Pump
ECO Mode
Space Heating tank
Backup heater pump
* First of all, to acced to the Heating circuit submenu go to the ―Setting‖ menu and find it further down.
Important Note: When the heating circuit 1/2 is set from YES to NO, the controller has to be switched "Auto
=> OFF => Auto" in the Operation menu to update the heating circuit outputs.
HEATING CIRCUIT 1
Posibilities
Factory setting
Yes / No
0,3 to 3
_ _ °C
_ _ (_ _ ) °C
-5K to + 5K
00:00 - 24:00
00:00 - 24:00
0 to -20K
00:00 - 24:00
00:00 - 24:00
0 to -20K
ON/10 - 25/OFF
60 - 120s
20 - 95
ON / OFF
P3
Yes / no
Off – P2 to P9
P4
Circulation Pump
P10
Mixing Valve +
P6
Mixing Valve -
T9
Water flow Temperature
T11
Outdoor Temperature
T12
Room Thermostat
No
To activate the function
1
Supply water temperature
Only view of the value
Only view of the values.
The value in the braket "(_ _)" is the calculated value.
Only view of the value
The adjustment must be done on the room thermostat
9H00
Day period start
16H00
Day period stop
Reduction of the temperature
-5K
during day period
23H00
Night period start
06H00
Night period stop
Reduction of the temperature
-5K
during night period
10 to 25 = Stop automaticaly in summer when outside temperature is
more than this level for more than 8 Hours.
22
ON = "Operation is Off" which means that Heating circuit is stopped.
OFF = "Operation is On" which means that there is no summer stop
whatever the temperature.
120s
Time duration for the complete valve cycle (Open / Close)
50
Upper limit for water injected in the heating circuit
OFF = > P3 and the backup space heating pump work independantely
OFF
ON => The backup space heating pump will be stopped when D.H.W
demand.
(can be defined manually as thermostat function block)
If yes, the space heating tank will be load with the bakup heater in
accordance with the water heating demand in the heating circuit.
no
The tank will be load at +10°C of the water temperature requested by
the curve.
OFF
Pump use for backup heater of the space heating tank
17
HEATING CIRCUIT 2
(Only available with systems 1 – 8)
Remark
P5
P7
P8
T10
T11
T12
loading