PowPak
|
Installation
Dimming Module with 0 –10 V-
Part of the Vive Family
RMJS-8T-DV-B
120 / 277 V~ 50 / 60 Hz 8 A
URMJS-8T-DV-B
RMJS-8TN-DV-B
RMJS-8T-DV-B-EM
120 / 277 V~ 50 / 60 Hz 8 A
0 –10 V- Control: 10 V- 60 mA
UL 2043 Plenum Rated
UL 924 Listed (RMJS-8T-DV-B-EM)
Compatible with ANSI E1.3 2001 (R2006), IEC 60929 Annex E
Note for Replacement:
RMxS and URMxS - the "S" model can replace the non-"S" model
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes (including periodic testing and maintenance of
emergency systems).
• Note: Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C) ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
PowPak
Dimming Module
Install in center of room to
maximize RF coverage.
Radio Powr Savr
Occupancy
Sensor
PowPak
30 ft
Dimming
(9 m) max
Module
Pico
Remote
Control
40 ft (12 m)
All Wireless
Transmitters must
be installed within 30 ft
(9 m) of the PowPak Dimming
Module with 0 –10 V-.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS.
• Do not use outdoors.
• Do not mount near gas or electric heaters.
• Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
• Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each system, ensure that you have:
One PowPak Dimming Module
At least one Wireless Transmitter
041588
041646
Rev. A
Rev. A
03/2018
03/2018
Load Status LED
Raise
Toggle
+
Lower
Radio Powr Savr Occupancy/Vacancy Sensor
PowPak Dimming Module with 0 –10 V-
(1 maximum)
(10 maximum)
Start Here
1
Mount, Wire, and Install 0 –10 V- Devices
and Lighting Fixtures
Consult third-party device installation guide
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
A Connect mains wiring (switched hot, neutral) to each fixture.
B Connect 0 –10 V- control (+ and – ) to each fixture.
2
Install PowPak Dimming Module with 0 –10 V-
Suggested Installation Location: Center of room to ensure proper RF coverage of area.
A PowPak Dimming Module with 0 –10 V- can be installed in a junction box or marshalling box using the conduit nut (provided) or with mounting
screws (not provided). Please consult local and national electric codes for proper installation.
If installing unit inside a junction box, please see Application Note #423 (P/N 048423 at www.lutron.com).
B Once installed, energize the PowPak Dimming Module with 0 –10 V-.
C Use the Toggle button " u " to toggle between high-end and OFF to verify ballast wiring.
D Use the Raise " " and Lower " " buttons to verify control wiring.
RMJS-8T-DV-B / URMJS-8T-DV-B
Junction Box
Line/Hot
(Black)
Switched Line/Hot (Red)
Neutral
Neutral (White)
1/2 in (21 mm) Knockout Opening
Conduit Nut
–
0 –10 V- to Fixtures*
+
3
Programming with a Vive Hub
A Use an iOS
or Android
B Download the Lutron
®
®
compatible device.
Vive app.
Vive
Pico Remote Control
(10 maximum)
Green/Yellow
Neutral
Switched Line/Hot
+
Violet
–
Gray
To additional 0 –10 V- fixtures
RMJS-8TN-DV-B
Junction Box
Line/Hot
(Black)
To Fixtures
Neutral
C Open the app and
Note: For further information on set
follow the instructions.
up, programming, and troubleshooting
with a Vive system, please refer to the
installation instructions included with the
Vive hub or visit www.lutron.com/vive
vive.lutron.com
Note: For programming the PowPak
Dimming Module without a Vive hub
see reverse side.
Customer Assistance www.lutron.com/support
At least one 0 –10 V- Fluorescent Ballast or LED Driver
Consult third-party 0 –10 V- fixtures installation guide for fixture-specific wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).
+
Link
Cal.
Test
60 mA maximum for the control lines. Switches up to 8 A total.
May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must comply with the
Radio Powr Savr Daylight Sensor
limits for a Class A device, pursuant to Part 15 of the FCC rules.
(1 maximum)
RMJS-8T-DV-B-EM
Fixture Earth
NEU
Sample
HOT
ballast shown
+
Regular
–
Utility Power
Emergency
Backup
Generator
1/2 in (21 mm)
Switched Line/Hot (Red)
Knockout Opening
To Fixtures
Neutral (White)
Conduit Nut
–
0 –10 V-
+
to Fixtures *
1/2 in (21 mm) Knockout Opening
Conduit Nut
* Use 18 AWG to 16 AWG (0.75 mm
Note: For periodic testing and maintanance of emergency systems, use the toggle button of
the RMJS-8T-DV-B-EM to ensure proper operation. Make sure PowPak buttons remain
accessible.
Note: Momentary power outages can envoke emergency mode on the dimming module. See
Troubleshooting section for details.
Default Functionality
Wireless Controls: All lights
On: 100% ; Favorite: 50%; Off: 0%
Occupancy Sensors
Occupied: All lights100% ; Unoccupied: All lights off
Daylight Sensor
All lights dim in response to daylight.
120 / 277 V~ Normal Feed
Neutral
Automatic
120 / 277 V~ Emergency Feed
Transfer
Switch
Neutral
Neutral
Line/Hot (Black)
Junction Box
Switched Line/Hot (Red)
To Emergency
Neutral (White)
Fixtures
–
0 –10 V- to
+
Emergency
Fixtures*
2
to 1.5 mm
2
) solid wire only