: Process Set value Low Limit. Minimum set value is defined with this parameter. It
changes according to the process input type and scale. (Default: -200)
: Process Set value High Limit. Maximum set value is defined with this parameter.
It changes according to the process input type and scale. (Default: 900)
: Display offset for process value. It can be adjusted from -10% of scale to 10%
of scale. It is added to the process display value. (Default: 0)
Note: If process input type selection(
,
,
,
parameters may need to be updated according to the input type selection.
: Control Menu Parameters
: This parameter determines, which output will be Process control output. If rLY is
chosen, process output is relay output, if SSr is chosen, process output is SSR output.
(Default: Ssr)
: Process Type Selection. It can be
: Process Control Type Selection. It can be
: If tune parameter is set to
automatically. This parameter is shown if
: Proportional band . It can be adjusted from %1 to %100.If
this parameter can be observed. (Default: 10.0)
: Integral Time.
It can be adjusted from
this parameter can be observed. (Default: 100)
: Derivative Time.
this parameter can be observed. (Default: 25.0)
: Output Control Period.
then this parameter can be observed. (Default: 10)
: Hysteresis value.
If
=
: Sensor Break Output Value.
: Soft Start Set value. Device operates in Soft Start mode, until the temperature reaches
Soft Start set value. (Default: no)
: Soft Start Control Output. This parameter determines soft start mode control output
percentage. (Default: 10.0)
: Soft Start Control time.
(Default:1)
: Alarm Menu Parameters
: Alarm Hysteresis value.
(Default: 0)
: Alarm Type selection. (Default:
:
Alarm Set Low Limit parameter. It can be adjusted from Operation Scale minimum to
Alarm Set High Limit. (Default: 0)
:
Alarm Set High Limit parameter. It can be adjusted from Alarm Set Low Limit to
Operation Scale maximum. (Default: 500)
: Alarm on Delay Time. It can be adjusted from 0 to 9999 seconds. (Default: 0)
:
Alarm off Delay Time. It can be adjusted from 0 to 9998 seconds. If it is higher than
9998,
, is seen on the screen and Alarm Latching Output is selected. (Default: 0)
) is changed,
,
,
,
, device start to calculate PID parameters
0 to 3600 second.If
It can be adjusted from
It can be adjusted from
It can be adjusted from %0 ile %50
, then this parameter can be observed (Default: 3)
It can be adjusted from
This parameter determines soft start mode control time
It can be adjusted from %0 ile %50 of the Scale(
)
,
,
,
,
and
or
.(Default:
or
.(Default:
=
. (Default:
0.0 to 999.9 second.If
1 to 150 second
of the Scale
%0 to %100.
)
)
)
=
, then
=
, then
=
,then
If
=
,
(
-
)
(Default: 0.0)
.
-
)
.
10