PR electronics 9410 Manual De Instrucciones página 19

Ocultar thumbs Ver también para 9410:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK
9420 Power Supply and 9410 Power Control with Backup.
Maintain a minimum distance of 50mm
between the 9420 Power Supply and
other modules.
General
The 9410 must be supplied from a Power Source with Double or Reinforced insulation to
Mains.
Alternatively use PR9420 Power Supply for installation inside or outside Zone2.
For installation in Zone 2
The 9410 Power Control Unit and 9400 Power Rail must be installed in an outer
enclosure having an IP protection of at least IP54 conforming to the
requirements of explosion protection Ex-n or Ex-e.
Transients are suppressed by an internal transient protection device, which is
set to a level not exeeding 40% of the rated voltage.
WARNING: Do not separate connectors when energized and an explosive gas
mixture is present.
WARNING: Do not install or remove modules from the Power Rail unless Area
is known to be Non Hazardous.
.
Revision date:
2008-06-10
9410 - Product Version 9410-001
Version Revision
V2 R1
9410QA01
Prepared by:
PB
Page:
3/3
17
Tabla de contenido
loading

Tabla de contenido