LERBAKKEN 10, 8410 RØNDE DENMARK.
FM Installation Drawing 5300Q502 Rev AH
Model 5331C,5331D, 5333C, 5333D and 5343B
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class I, Zone 0, IIC
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Only passive, or non-energy
storing devices such as RTD's
and Thermocouples may be
connected.
Model 5335C, 5335D, 5336D, 5337D
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class I, Zone 0, IIC
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Revision date:
2014-03-31
20
WWW.PRELECTRONICS.COM
1
2
6
3
5
4
SENSOR
1
2
6
3
5
4
SENSOR
Version Revision
V4R0
5335V115-ES
5335QE01
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
‐
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected
to any associated apparatus which
uses or generates more than 250
VRMS
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
‐
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected
to any associated apparatus which
uses or generates more than 250
VRMS
Page:
5/9