4.0 Ventilation

When the cylinder below the counter is enclosed in a space equal to
A
or greater than 6,712 cubic inches (0.11 cubic meters) , additional
ventilation is not required.
When the cylinder below the counter is enclosed in a space less than
6,712 cubic inches (0.11 cubic meters), ventilation is required.
For Optimum Performance
Ensure appliances that generate heat are not
near the product
Ensure the base and sides are not obstructed
Ensure the base and sides are not located in
an area where they are vulnerable to damage
or obstruction
4.1 Ventilation - Example A
Spaces surrounding the cylinder that are equal to or greater than 6,712 cubic inches
(0.11 cubic meters) do not require additional ventilation.
This example would not require additional ventilation: 30" x 30" x 8" = 7,200 cubic inches
8"
If multiple U-Chill
units are installed into the same space, the non-vented allowance is 6,712
TM
cubic inches per installed U-Chill
.
TM
4.2 Ventilation - Example B
Spaces surrounding the cylinder that are less than 6,712 cubic inches (0.11 cubic meters)
require additional ventilation. A small vent into a larger partition or into ambient air should be
specified in the back partition of the space. This will allow for proper airflow.
The vent should have an area of at least 14 square inches.
30"
(back partition)
12"
12"
This example would require additional ventilation:
12" x 12" x 30" = 4,320 cubic inches
30"
30"
vent example size:
1-1/2" x 9-1/2" = 14.25 square inches
(back partition)