Advanced Programming - DIEL MT 200 E Manual De Instalacion Y Uso

Idiomas disponibles
  • ES

Idiomas disponibles

MT 200 E
ENG
P: PRE-ALARM, default 140
A: ALARM (CONTROL UNIT
INTERVENTION), default 160
L: FANS SHUTDOWN, default 90 (not
required for configuration 0 and 2)
H: FANS IGNITION, default 100
(not required for configurations 0 and 2)
C: PROTECTION OF FAN BEARINGS,
default 1, C=0 not active, C=1 fan ignition
once a day 5 min, C=2 fan ignition once a
week 5 min
At the end of the programming cycle, the control unit performs the test on all
the light sectors and positions itself in the main menu displaying the maximum
measured temperature and the relative channel.
For safety reasons, the time required for programming is in any case checked.
Over one minute from the start of the programming phase, the same is
interrupted and not saved (therefore the previously set parameters remain
active) after which it returns to automatic display mode.

ADVANCED PROGRAMMING

It allows to program independent thresholds
To access the ADVANCED PROGRAMMING menu, refer to the
PROGRAMMING paragraph, choice 4.
CHANNEL 1 is proposed, as enabled default,
to disable the channel set the value of the first
display to 0 with the keys
and press
to confirm.
The following values are then proposed, modifiable with the keys
, to
be confirmed with the key
.
- 27 -
loading