Error
F) fan stop work-
ing
G) lack of frezon
H) too long oper-
ating or inter-
mittent
I) Equipment is in
operation, but
low ability
J) The suction side
of compressor is
frosted
K)system's ab-
normal noise
L) low Indoor
temperature, low
temperature
alarm
Possible Causes
fan current contactor impassability check contactor coil, replace it if
fan motor protection is open
leakage of freon circuit
lack of freon
temperature controller does not
work or setting error
too big thermal load
The compressor working poor
blockage of freon filter
lack of freon
abnormal temperature expansion
valve
airflow problem
lack of freon
blockage of refrigerant system fil-
ter
Pipeline vibration
Compressor's noise
Expansion valve is sputtering
The connection part of unit struc-
ture loose,cause clash for shaking.
impact or friction between moving
parts and other components
Improper installation of door plank correct installation
Friction of fan impeller and tuyere
Oil shortage or wear of fan bearing fill oil or replace
the connecting bolt of fan is loose
Compressor still work after reach-
ing a certain temperature: there is
something wrong with the tem-
perature
The heater doesn't work: The
heating resistance is without elec-
tricity or under voltage
The heater doesn't
work:resistance burned
The heater doesn't work:the tem-
perature probe problem
Solutions
damage
check insulation of fan motor
winding or relax drive belt
Make freon circuit pressurization 4
bar, leak detection; repair, vacuum
supply, freon filling
fill fluorine
Check the thermo-
stat;Reset;Replace the mother-
board if damage
lower the heat load
check, replace
check, replace
fill fluorine
check and clean, replace it if nec-
essary
check filter,fan and air flue
fill fluorine
check, replace it if necessary
support, fixed the pipe
check, replace it if necessary
check,fill fluorine
check, rule out
check,exclude
adjust clearance
Tighten the bolt
check, replace it if necessary
check the protection and circuit
replace
replace probe
41