Wiring according to EMC
For an EMC−compliant wiring, please observe the following items:
)
Note!
In order to avoid potential differences between the nodes, use an
ƒ
equalizing conductor with a large cross−section (reference: PE).
Install control cables separately from motor cables.
ƒ
Apply the shields of the data lines on both sides.
ƒ
Observe the further notes on EMC−compliant wiring in the instructions of
ƒ
the basic device.
EDK2191DB DE/EN/FR/ES/IT 1.0
Electrical installation
Wiring according to EMC
l
3
27