CHECK PARAMETERS
NOTE
(1) = version Y
14. 1
T H E R M O M A G N E T I C
SWITCHES FANS
14.2
T H E R M O M A G N E T I C
SWITCHES COMPRESSORS
14.3
TRANSDUCERS
PRESSURE SWITCHES
KEY
PA
High pressure switch
PB
Low pressure switch
TRA
High pressure transducer
TRB
Low pressure transducer
All units are thoroughly tested in the
factory before shipping. Nonetheless,
it is always good practice to check all
control and safety systems after a
reasonable period of operation.
All the control operations must be
carried out by qualified personnel; the
wrong settings on the above devices
can cause serious damage to the unit.
14.3. 1 High pressure switch
The high pressure switch stops the
compressor (generating the relative
alarm) when the delivery pressure
exceeds the set value.
The control of its correct working can
be made by closing the air suction
on the exchanger (in cold mode) and,
keeping the high pressure gauge under
control, checking it intervenes upon
reaching the calibrated value.
CALIBRATION OF CHECK AND SAFETY
14
PARAMETERS
Cooling set point
Heating set point
Antifreeze intervention
Total differential
Autostart
2000
2250
n° Ventilatori
4+4
4+6
MTV 1
9 A
9 A
MTV 2
9 A
9 A
MTV 3
9 A
13 A
MTV 4
9 A
13 A
2000
2250
MTC1
53 A
53 A
MTC1A
53 A
53 A
MTC1B
/
/
MTC2
53 A
53 A
MTC2A
53 A
53 A
MTC2B
/
/
MTC3
53 A
57 A
MTC3A
53 A
57 A
MTC3B
/
/
MTC4
53 A
57 A
MTC4A
53 A
57 A
MTC4B
/
/
2000
PA a freddo
27
PA a caldo
H
27
PB
HL
20
TRA
27
TRB
1
WARNING
If the switch does not trip at the
calibrated value, stop the compressor
immediately and identify the cause.
Reset is manual and only enabled
once the pressure drops below the
differential value. (For the set and
differential values, see the technical
manual).
14.3.2 Low pressure switch
The low pressure switch stops the
compressor (generating the relative
alarm) when the suction pressure
drops below the set value. The control
of its correct working can be made
(after about 5 minutes of operation) by
slowly closing the tap on the liquid pipe
and, keeping the low pressure gauge
under control, checking it intervenes
upon reaching the calibrated value.
min.
standard
4 / -6 (1)
7 / -6 (1)
°C
°C
35
48
-9
3
°C
3
5
°C
2500
2800
3000
6+6
6+6
6+6
13 A
13 A
13 A
13 A
13 A
13 A
13 A
13 A
13 A
13 A
13 A
13 A
2500
2800
3000
57 A
57 A
53 A
57 A
57 A
53 A
/
/
53 A
57 A
53 A
53 A
57 A
53 A
53 A
/
53 A
53 A
57 A
57 A
53 A
57 A
57 A
53 A
/
/
53 A
57 A
53 A
53 A
57 A
53 A
53 A
/
53 A
53 A
2250
2500
2800
27
27
27
27
27
27
20
20
20
27
27
27
1
1
1
WARNING
If the switch does not trip at the
calibrated value, stop the compressor
immediately and identify the cause.
Reset is manual and only enabled
once the pressure rises above the
differential value. (For the set and
differential values, see the technical
manual).
14. 1 .3 Anti-freeze control
The anti-freeze control, managed
by electronic regulation and by the
temperature probe at the evaporator
outlet, has the job of preventing the
formation of ice when the water
flow rate is too low. The control of
its correct working can be made by
gradually increasing the anti-freeze
set until it exceeds the outlet water
temperature and, keeping the water
max.
14
50
4
10
auto
3300
3600
8+8
8+8
17 A
17 A
17 A
17 A
17 A
17 A
17 A
17 A
3300
3600
53 A
57 A
53 A
57 A
53 A
57 A
57 A
57 A
57 A
57 A
57 A
57 A
53 A
57 A
53 A
57 A
53 A
57 A
57 A
57 A
57 A
57 A
57 A
57 A
3000
3300
3600
27
27
27
27
27
27
20
20
20
27
27
27
1
1
1
27