18
Connections RBMP1 <--> PSR2 (PSE/PSU/PSC3000) and PSF2 (PSC7000/1)
Two-way connection: the RBMP1 may be situated
along any point of the cable route
RBMP1
Between the fi rst and last
PSR2/PSF2, the distance
PSR2
(meaning the route of the
connection cable) must be
1000 m long maximum
PSCA2
PSCA2
Cable* NOT INCLUDED
Suggested type: non-
screened, twisted multi-
paired (CAT 5 – U/UTP
– AWG24)
Each unit is identifi ed by the RBMP1 thanks to progressive sequential numbering, independently
from the position along the connection cable route; such numbering (also known as an address)
must be set on the relative DIP Switch on the peripheral unit's board (Entrance or Exit units and
PSR2/PSF2
*The PSR2 cards equip the the PSE/PSU/PSC3000 units, while the PSF2s equip the
* AWG24 cable connection colours
√ White/Orange braided on GND
√ White/Green braided to split:
• White on A
• Green on B
Insulate the remaining pairs.
PS BARCODE -
PSR2
automatic cash register)
A
T THE SUBSEQUENT
PSC7000/1 cash registeres.
Hardware and wiring
RBMP1
* PSR2/PSF2 (ENTRANCE
AND EXIT CONNECTABLE ON EITHER
TERMINAL BOARDS 1 OR 2)
A
T THE SUBSEQUENT
Cable* NOT INCLUDED
Suggested type: non-
screened, twisted multi-
paired (CAT 5 – U/UTP
– AWG24)
* PSR2/PSF2 (ENTRANCE AND EXIT CONNECTABLE
ON EITHER TERMINAL BOARDS 1 OR 2)
PSR2/PSF2