Solution to problems
Problem
The wind turbine does not
rotate
The inverter DOES NOT
supply power with the wind
turbine in operation
Possible cause
Emergency stop button is
activated
Stop button on the monitor
was pressed.
Fault of the grid or problem
in the inverter
High wind
Polarity of the wires
inverted.
High temperature
The anemometer is
configured and there are
revolutions but there is no
wind measurement
Values of the grid lacking or
out of range
The data wire between the
inverter and the interface is
disconnected
Solution
Disactivate the button
by turning it slightly
to the left
On the monitor click
on the button again to
deactivate it
The interface has
detected an error in
the synchronism with
the grid and stops the
turbine
It is necessary to wait
until the wind drops
to below the level
programmed
Check the polarity of
the DC wires between
the interface and the
inverter
Check to see if the
temperature of the
regulator is high. If it
is, it is necessary to
wait until it cools
Check the connection
of the anemometer
because RPMs are
being detected but
there is no wind
reading.
Check the
parameters of the
grid
Check to see if it is
connected; if it is not,
connect it
30