InDepth Light Fixture Instructions
For T-Grid Mounting
1.
Turn off the power at the main fuse/breaker box.
2.
Carefully open carton and remove light fixture from
packaging.
3.
Locate fixture access plate and slide to remove it (Fig. 1).
NOTE: Some arrangements require two junction boxes
and have multiple connection. Shown here is the most
common.
4.
Remove appropriate knockout(s) for power supply wiring.
Remove screw and push
access plate to remove.
Figure 1. 
NOTE: Fixture weights are below. Ensure grid location is rated
for fixture weight before moving to next step. If unsure use
cable to support fixture to appropriate support beam above
fixture using the circular holes in the corner tabs (Fig 2).
2' x 2'
28.8 lb.
Figure 2. 
5.
Pass fixture through the grid at a 45 degree angle and
lay fixture into the grid (Fig. 3).
Figure 3. 
6.
Grid clips are provided for additional retention to ceiling
system. Attach grid clips using supplied screws to the
aluminum frame of the fixture, and the T-Grid (Fig. 4)
2
COOPER LIGHTING SOLUTIONS
1' x 4'
2' x 4'
30.6 lb.
40.5 lb.
IB519120EN
Installation instructions
Figure 4. 
7.
Remove a knockout bring in the supply line. Attach the
ground wire to the ground supply wire. Using the linear
disconnect, attachthe black (line) wire to the black
supply wire, and the white (neutral) wire to the white
supply wire (Fig. 5).
Figure 5. 
NOTE: The fixture is compatible with 0-10V, STEP, DALI,
Lutron, and LV dimming. If installing dimming wires follow
your dimmer instructions for wiring to the fixture.
NOTE: This fixture is compatible with battery backup systems
including the Surelites EBPLED7W and EBPLED14W. If using
a battery backup system remove driver cover plate to access
LED load wires and follow battery backup wiring instructions
(Fig. 5). Ensure driver cover plate is reinstalled after wiring.
8.
Tuck all wires and wire nuts into the fixture junction box,
replace electrical access plate, and snap securely into
place.
9.
To clean fixture use a small amount of water on a cloth
and wipe the lens. Do not use chemicals on the lens as
this could cause damage.
10. Turn breaker on. Use wall switch to verify light turns on.
To Remove or Replace Lens
1.
Disconnect power.
2.
Remove fixture from ceiling.
3.
Remove 2 screws holding extrusion in place. Slide
extrusion and brackets away from fixture.
4.
Slide lens out. (See Figure 6).
Figure 6. 