Starting from a preset humidity and temperature Setpoint, the user can modify the operation
of the unit manually or by setting the program to start or stop on a specified day, hour and minute
(optional - for machines equipped with time card).
This application also offers the possibility of a special mode of programming which can be
done by the personnel in charge of the maintenance and control of the equipment. This personnel
will be able to modify various parameters such as: Setpoint differential, maximum temperature and
time limits, defrosting temperatures (ON/OFF), delayed operation, units, etc...
It also includes various alarms which can be viewed on the FX 05 display, as well as a relay
alarm.
ANALOG ENTRY
AI1 Return Temperature
AI2 Condenser Temperature
AI3 3-way Resistance Valve
Temperature
AI4 Relative Humidity
4.
TECHNICAL CHARACTERISTICS.
CARACTERISTICS
Dehumidification Capacity
Power Output w (*)
COMPRESSOR
Units.
Type
Voltage.
Frequency.
Consumption. (Amp)
Nominal Power. (cv)
FAN
Type.
Units.
Flow. (m3/h)
Consumption. (Amp)
Voltage.
OTHER DATA
Nominal consumption
Refrigerant.
Weight in Kg + Electric Battery
Weight in Kg + A.C. Battery
* The calculation of power output was done based on exterior air Temperature of 28 ºC and 75%
Humidity.
DIGITAL ENTRY
DI1 HP Switch
DI2 LP Switch
DI4 Thermal compressor
(Inside the compressor)
CDP-2
2,1 lts/h
4.277 W
1
Hermetic
220V II
380V III
220V II
50 HZ
6,01
2
7,04
1
Centrifugal
1
700
1,1
220 V
7,1 Amp
R-407C
46
50
DIGITAL OUTPUT
DO1 General alarm
DO2(ON/OFF) Compressor
DO3(ON/OFF) Fan
DO4 (ON/OFF )3-way Resistance
Valve
MODEL
CDP-3
3,1 lts/h
4,2 lts/h
5.313 W
7.068 W
1
Hermetic
Hermetic
380V III
220V II
50 HZ
2,3
9.91
1 1/4
Centrifugal
Centrifugal
1
800
1,1
220 V
8,2 Amp
11,01 Amp
R-407C
49
54
ENGLISH
ANALOG
OUTPUT
CDP-4
CDP-5
5,1 lts/h
8.473 W
1
Hermetic
380V III
220V II
50 HZ
50 HZ
3,3
9,4
1 5/8
Centrifugal
1
1.000
1.200
1,1
1,1
220 V
220 V
10,5 Amp
R-407C
R-407C
64
69
1
380V III
4,3
2
1
66
72
29