Description
3.1 General
Scale factor, factory-programmed
7 digit LCD display, height 8 mm
Counting range 0 ... 9999999, no decimal point
Data retention: EEPROM
DIN housing 48 x 24, dark grey
Power supply 10 ... 30 V DC, max. 25 mA
3.2 Connection and functions
Terminal assignment
Codix
3.2.1
140
Codix 140: pulse counter, fast and slow (bounce-
free) input, electronic or manual Reset possible.
Function and terminal assignment
(the bold indications correspond to the text on the device)
Ter-
Function
minal
1
10 – 30 V DC, Supply voltage +Ub
2
GND, 0 V DC
3
GND, 0 V DC
4
INP PNP, fast counting input: the counter
increments the value by one at each
bounce-free voltage pulse > 3,5 V at ter-
minal 4
5
INP NPN, slow counting input: the counter
increments the value by one at each volt-
age drop to < 2 V at terminal 5
6
RESET MANUEL ENABLE
Reset key enable input: when terminal 6 is
connected to GND or to 0 V (< 2 V), the
key allows resetting the counter to 0
7
RESET, Reset input, when terminal 7 is
connected to GND or to 0 V (< 2V), the
counter is reset to 0 (electronic Reset)
8
n. c. is not used with the standard counter
3.2.1.1 Function of the front key
Pressing the red front side key resets the counter to
0. This function is only active when input 6 is set to
0 V or connected to GND.
Output 8 only for
Codix 142
Output load
Codix
3.2.2
142
Service counter with 2 messages, "Service" and
"PreService", and one output. Fast and slow
(bounce-free) input, electronic and manual Reset
possible. With one single Reset, the counter con-
tinues counting up to the following service interval.
No resetting to 0 occurs. If the Reset key or the
Reset input is activated a second time within
4 s, the device is reset to its delivery condition.
(The counter value is reset to 0, the message dis-
play preselections are reset to 5000 and 4900!).
Example: service after 5000 pulses, "SErViCE"
Pre-alarm at 4900 pulses, "PrESErV"
(= 5000 – 100)
If a pre-alarm is set "PrESErV": the following mes-
sage is displayed alternately with the current value
The recommended setting is 100 pulses before the
service preselection. In the above example, the
pre-alarm occurs when the counter reaches 4900
and it remains set until the service preselection is
reached.
After 5000 pulses, the following message is dis-
played alternately with the current value
and the output at terminal 8 becomes active. This
alternating display and the output set remain active
until the counter is reset. For example, if the coun-
ter is reset when it displays the value 6000, the
blinking display and the output are reset. The dis-
play shows for 4 s the new preselection value, and
then switches to the current counter value. The
message "SErViCE" and the output will be set ac-
tive again when the counter reaches 11000
(6000+5000).
Function and terminal assignment
(the bold indications correspond to the text on the device)
Termi-
Function
nal
1
10 – 30 V DC,
Supply voltage +Ub
2
GND, 0 V DC
3
GND, 0 V DC
4
INP PNP, fast counting input: the counter
increments the value by one at each
bounce-free voltage pulse > 3,5 V at ter-
minal 4
5
INP NPN, slow counting input: the coun-
ter increments the value by one at each
voltage drop to < 2 V at terminal 5