Table 3: List of parameters related to the accessory
Param. Description
P013
DO3 to
DO1 Status
(*)
P027 Accessory
Config.
P275
DO1
Output
(*)
Function
P276
DO2 Output
Function
(*)
P277
DO3 Output
Function
(*)
Infrared Remote Control and I/O
CFW100-IOADR
Adjustable Range
0 to 7 (hexa)
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
0 = No Accessories
1 = Reserved
2 = CFW100-IOAR
3 = CFW100-CCAN
4 = CFW100-CBLT
5 = Reserved
6 = CFW100-IOADR
0 = Not Used
1 = F* ≥ Fx
2 = F ≥ Fx
3 = F ≤ Fx
4 = F = F*
5 = Not Used
6 = Is > Ix
7 = Is < Ix
8 and 9 = Not Used
10 = Remote
11 = Run
12 = Ready
13 = Without Fault
14 = Without F070
15 = Not Used
16 = Without F021/F022
17 = Not Used
18 = Without F072
19 = 4-20 mA OK
20 = Not Used
21 = Clockwise
22 to 23 = Not used
24 = Ride-Through
25 = Pre-Charge OK
26 = With Fault
27 = Not Used
28 = SoftPLC
29 to 34 = Not Used
35 = Without Alarm
36 = Without Fault/Alarm
37 = Function 1 Application
38 = Function 2 Application
39 = Function 3 Application
40 = Function 4 Application
41 = Function 5 Application
42 = Function 6 Application
43 = Function 7 Application
44 = Function 8 Application
See options of P275
See options of P275
Expansion Module
Factory
Proper.
Setting
13
0
0
CFW100 | 9
ro
ro
cfg
cfg
cfg