Connectivity
You may set up a local network between various data loggers linked in any of the following arrangements. This will
allow you, among other things, to use the device configured as master data logger to print data from any other
data logger or upload data from any data logger to a PC.
IMPORTANT: Each unit must be assigned a different slave address.
Not connected to a PC:
Maximum 7 data loggers, 1 in master mode and 6 in slave mode.
MASTER
SLAVE 1
Recorder
Recorder
Tr-
Tr
Gnd
Tr-
Tr
Gnd
+
+
21
22
23
21
22
23
Connected to a PC:
Maximum 127 data loggers in slave mode connected to a PC (master).
Recommended cable: AKO-15586
SOFTRegis
AKO-5003
AKO-5004
Installing the thermal paper roll
AKO-15742/15752/15782 only
-With the unit connected to the network, open the front cover and push the release lever (1) back.
-Place the paper roll in the position shown on the image.
-Insert the end of the paper roll through the bottom slot in the
printer until it begins to feed through. As soon as the paper
appears in the top slot, the device will stop feeding.
-Return the release lever to its initial position. The printer is now ready
to print.
-Press the E key to feed the paper through.
-Press the D key for express printing.
To print data, the data logger has to have at least one entry recorded.
The required printing time will depend on the entry interval
configuration (default is 15').
IMPORTANT: The printer paper is thermal and can only be printed on one side. Make sure you insert it
properly.
SLAVE 2
SLAVE 6
Recorder
Recorder
Tr-
Tr
Gnd
Tr-
Tr
+
+
21
22
23
21
22
RS-485
(MODBUS)
AKO-80039
Converter
RS-485
+
Gnd
23
SLAVE 1
SLAVE 2
Recorder
Recorder
Tr-
Tr
Gnd
Tr-
Tr
+
+
GND
21
22
23
21
22
1
17
SLAVE 127
Recorder
Gnd
Tr-
Tr
Gnd
+
23
21
22
23
RS-485
(MODBUS)