NOTE: Install the mounting bracket and drill the holes in the
wall according to the wall structure and the correspond-
ing mounting points on the mounting bracket. (The
mounting brackets vary according to the model.)
Correct orientation
of installation plate
4. Determine the hole positions according to the diagram
detailed in Figures 5A, 5B and 5C. Drill one (1) hole 3 &
3/4" ( 95mm), slanting slightly to the outside.
NOTE: Always use wall hole conduit when drilling metal
grid, metal plate, etc.
15 SEER MODELS
11.5" (293mm)
19 SEER MODELS
6" (150mm) or more
from the ceiling
Pipe hole
2 1/5" (58mm)
Incorrect orientation
of installation plate
Figure 4
.8"
40.5" (1030mm)
Figure 5A
Hooker Part
Hooked Part
49" (1250mm)
32" (815mm)
Pipe hole
Indoor unit outline
Figure 5B
Figure 5C
Refrigerant Piping & Condensate Piping
Installation:
5. Drain hose should be installed with a slight downward
slope. (See Figure 6.)
Indoor
Drain hose should NOT be installed as shown in Figure 7.
Do not block water flow by a rise.
6. When connecting extension drain hose, insulate the con-
necting part of the extension drain hose with a shield
pipe. Do not allow the drain hose to be slack.
7. REFRIGERANT PIPING INSTALLATION:: For the left-
hand and right-hand piping, remove the pipe cover from
the side panel. (Figure 8.)
8. For the rear right-hand and rear left-hand piping, install as
shown in Figure 9.
4
Wall
Outdoor
Figure 6
Do not put the end of
drain hose into water.
Figure 7
Figure 8