104 mm
B501RF
72 mm
+
136 g
48 g
(66 g)
Figure 1: B501RF Mounting
≤ M4
Figure 2: Attaching Sensor Head to Base
LINE UP MARK ON
SENSOR HEAD
WITH BULGE ON
BASE AND TURN
CLOCKWISE
Figure 3a: Activation of Tamper Resist Feature
PLASTIC LEVER
Figure 3b: Removing Sensor Head From Base
USE A SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC IN THE DIRECTION OF THE ARROW
N200-300-00
WIRELESS MULTI-CRITERIA FIRE SENSOR
INSTALLATION AND MAINTENANCE INSTRUCTIONS
32 mm
=
250 g
50-60 mm
BULGE
MARK ON
SENSOR HEAD
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARDS CENTRE OF
BASE
Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK
NRX-SMT3
DESCRIPTION
The NRX-SMT3 radio sensor is a battery operated RF device designed for
use with the NRXI-GATE radio gateway. It contains a wireless transceiver
40°C
and runs on a Notifier addressable fire system (using a compatible
proprietary communication protocol).
It is a multi-criteria smoke and heat detector (58
-30°C
sensor adds further detection ability and increased immunity to false alarms.
The sensor plugs into the B501RF wireless sensor base.
This device conforms to EN54-25, EN54-5 (Class A1R) and EN54-7. It
complies with the requirements of 2014/53/EU for conformance with the
RED directive.
SPECIFICATIONS
Supply Voltage:
Standby Current:
Red LED Current Max: 4mA
Re-sync time:
Batteries:
Battery Life:
Radio Frequency:
RF output power:
Range:
Relative Humidity:
INSTALLATION
This equipment and any associated work must be installed in accordance
with all relevant codes and regulations.
Figure 1 details the installation of the B501RF base.
Spacing between radio system devices must be a minimum of 1m
Figure 2 details attaching the sensor head to the base.
Anti-Tamper Features
The base includes a feature that, when activated, prevents removal of the
sensor from the base without the use of a tool. See Figures 3a and 3b for
details on this.
Head Removal Warning - An alert message is signalled to the CIE via the
Gateway when a head is removed from its base.
Figure 4 details the battery installation and the location of the rotary
address switches.
Batteries should only be installed at the time of commissioning
Using these battery products for long periods at temperatures below
-20°C can reduce the battery life considerably (by up to 30% or more)
Observe the battery manufacturer's precautions for use and
SETTING THE ADDRESS
Set the loop address by turning the two rotary decade switches on the
underside of the sensor (see figure 4), using a screwdriver to rotate the
wheels to the desired address. The device will take one sensor address
on the loop. Select a number between 01 and 159 (Note: The number of
addresses available will be dependent on panel capability, check the panel
documentation for information on this).
PROGRAMMING
To load network parameters into the RF sensor, it is necessary to link the RF
gateway and the RF sensor in a configuration operation. At commissioning
time, with the RF network devices powered on, the RF gateway will
connect and programme them with network information as necessary. The
RF sensor then synchronises with its other associated devices as the RF
mesh network is created by the gateway. (For further information, see the
Radio Programming and Commissioning Manual - ref. N200-306-00.)
NOTE: Do not run more than one interface at a time to commission
devices in an area.
C Rate-of-Rise). An infra-red
o
3.3 V Direct Current max.
@ 3V: 120 µA (typical in normal operating mode)
35s (max time to normal RF communication from
device power on)
4 X Duracell Ultra123
4 years @ 25
C
o
865-870 MHz;
14dBm (max)
500m (typ. in free air)
10% to 93% (non-condensing)
Important
Warning
requirements for disposal
E N G L I S H
I 56- 4205- 002
I56-4205-002
loading

Resumen de contenidos para Honeywell NOTIFIER NRX-SMT3

  • Página 1 (For further information, see the Radio Programming and Commissioning Manual - ref. N200-306-00.) NOTE: Do not run more than one interface at a time to commission devices in an area. N200-300-00 I56-4205-002 Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK...
  • Página 2 EN54-5: 2000 - Class A1R / A1: 2002 THERMISTOR [email protected] Heat detectors OPTICAL SENSING EN54-7: 2000 / A1: 2002 / A2: 2006 CHAMBER Smoke detectors Patents Pending N200-300-00 Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK I56-4205-002...
  • Página 3 I TA L I A N O NRX-SMT3 ISTRUZIONI DI INSTALLAZIONE E MANUTENZIONE PER SENSORE RADIO ANTI-INCENDIO A TRIPLA TECNICA DI RIVELAZIONE DESCRIZIONE 104 mm Il sensore NRX-SMT3 è un dispositivo a radiofrequenza alimentato a batteria, progettato per essere impiegato con il gateway radio NRXI-GATE. 40°C Contiene un ricetrasmettitore e viene integrato in un sistema antincendio B501RF...
  • Página 4 DI RITENUTA DELLA CALOTTA DEFLETTORE 0333 16 DOP-IRF015 Dichiarazione di Conformità UE Il fabbricante, Notifier by Honeywell dichiara COPRI CAMERA Pittway Tecnologica S.r.l. che il tipo di apparecchiatura radio NRX-SMT3 Via Caboto 19/3, 34147 Trieste, è conforme alle Direttiva 2014/53/EU...
  • Página 5 (mesh) vía radio (para más información, consultar el Manual de programación y puesta en funcionamiento vía radio.) N200-300-00 I56-4205-002 Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana...
  • Página 6 Puede solicitar el SENSOR ÓPTICO AC: 2012 documento a: [email protected] EN54-5: 2000 / A1: 2002 EN54-7: 2000 / A1: 2002 / A2: 2006 Patente pendiente N200-300-00 I56-4205-002 Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana...
  • Página 7 NRX-SMT3 D E U T S C H FUNK MULTIKRITERIEN RAUCHMELDER INSTALLATIONS- UND WARTUNGSANLEITUNG BESCHREIBUNG 104 mm Der Funkmelder NRX-SMT3 ist ein batteriebetriebenes HF-Gerät für den Einsatz mit dem Funk-Gateway NRX-GATE. Es beinhaltet einen drahtlosen Sender/ 40°C Empfänger und wird über ein adressierbares Brandmeldesystem betrieben. (mit B501RF 32 mm Einsatz eines kompatiblen, proprietären Kommunikationsprotokolls).
  • Página 8 Angemeldete Patente Abbildung 5: Position des Testmagneten DOP-IRF015 Pittway Tecnologica S.r.l. Vereinfachte EU-Konformitätserklärung Via Caboto 19/3, 34147 MARKIERUNG AM Hiermit erklärt Notifier by Honeywell, dass der Trieste, Italy MELDERSOCKEL Funkanlagentyp NRX-SMT3 der Richtlinie EN54-25: 2008 / AC: 2010 / 2014/53/EU entspricht.
  • Página 9 à ce sujet). Insérer la tête du détecteur sur son socle et tourner la dans le sens des aiguilles d’une montre jusqu’au verrouillage N200-300-00 Honeywell Life Safety SA, Liege Airport Business Park B50, 4460 Grâce-Hollogne - België I56-4205-002...
  • Página 10 Une attention particulière doit être accordée à l’environnement lors du choix des détecteurs et de leur emplacement. N200-300-00 Honeywell Life Safety SA, Liege Airport Business Park B50, 4460 Grâce-Hollogne - België I56-4205-002...